SmartPLC SafeLine AC4S with fieldbus interfaces
DisableLogging
BOOL
EnableStartupTest
BOOL
Chan_B_first
BOOL
* ...
Default value
>
Process data
Parameter
Data type
S_IN_cond_dep
SAFEBOOL
>
was created by a local output
Transmission of the event
messages to OSC of the device
Control execution of the start-up
test
Required sequence of the signal
state changes
Description
Safe process signal
TRUE
Test signal is evaluated
Following states of the state diagram
FALSE
are transmitted to the OSC: *
S_ON
S_OFF
S_Test
S_Error
S_Init (HW-Error)
TRUE
Following states of the state diagram
are transmitted to the OSC:
S_Test
S_Error
S_Init (HW-Error)
FALSE
No start-up test *
TRUE
Start-up test is executed; slave waiting
for start-up sequence OFF  ON
FALSE
Channel A = TRUE before
channel B = TRUE
TRUE
Channel B = TRUE before
channel B = TRUE
Possible values
FALSE
Safe OFF or error state
TRUE
Safe ON and no error state