SmartPLC SafeLine AC4S with fieldbus interfaces
>
Output parameters
Parameter
Data type
xPS
BOOL
xPM
BOOL
xEF
BOOL
xSE
BOOL
xPF1
BOOL
xPF2
BOOL
wVoltage1
WORD
wVoltage2
WORD
iSymmetry
INT
xReady
BOOL
xBusy
BOOL
xError
BOOL
wDiagnostic
WORD
Diagnostic codes:
0x0000
No specific error is set
120
Description
Voltage source (Power Source)
Power24-Modul (PM)
Earth fault
Status of the earth fault detection
Voltage <22.5 V (power fail 22.5 V)
Voltage <19.0V (power fail 19V)
Voltage AS-i+ to AS-i- in mV
Voltage FE to AS-i in mV
Symmetry in % (-100% ... +100%)
Signal indicates whether the execution
of the FB is completed.
Signal indicates whether the FB is
being executed.
Signal indicates whether errors
occurred while the FB was executed.
Diagnostic information
Possible values
FALSE
Unit is supplied via Aux.
TRUE
Unit is supplied via AS-i.
FALSE
Power24 module missing.
TRUE
Power24 module is inserted.
FALSE
No earth fault
TRUE
Supply voltage is asymmetric,
earth fault suspected.
FALSE
Earth fault detection does not
provide valid data (e.g. when
AS-i voltage is lacking).
TRUE
Earth fault detection provides
valid data.
FALSE
No AS-i power fault (Classic
APF)
TRUE
AS-i power fail (Classic APF),
i.e. AS-i voltage is below
22.5 V
FALSE
No AS-i power fail (24V-APF)
TRUE
AS-i power fail (24V-APF), i.e.
AS-i voltage is below 19.0 V
0xFF9C
-100%
...
...
0x0000
0%
...
...
0x0064
+100%
FALSE
FB is inactive or being
executed.
TRUE
FB execution is completed.
FALSE
FB is deactivated or FB
execution is completed.
TRUE
FB execution has started but is
not yet completed.
FALSE
FB is disabled or is being
executed or FB was executed
without error.
TRUE
An error occurred while the FB
was executed.
→ List below (Diagnostic codes)