SmartPLC SafeLine AC4S with fieldbus interfaces
>
Get_ASi_Data
Function block type:
Function block (FB)
Library:
ACnnnn_Utils.library
Symbol in CODESYS:
>
Description
The FB reads the following data from the selected AS-i master and stores the values in a structure
variable of data type ASI_DATA (→
List of activated slaves – LAS
List of detected slaves – LDS
List of projected slaves – LPS
List of configuration errors – LCE
List of configuration errors - additional slave – LCEAS
List of configuration errors - missing slave – LCEMS
List of peripheral faults – LPF
List of double address errors – LDAE
Configuration data image – CDI
Projected configuration data – PCD
Input parameters of the AS-i slaves
Outputs parameters of the AS-i slaves
>
Input parameters
Parameter
Data type
xEnable
BOOL
enASi_Master
ASI_MASTER
pASi_Data
POINTER TO
ASI_DATA
ASI_DATA (STRUCT)
Description
Control activiy of the FB
Select AS-i master
Structure variable in which the read
data is to be stored.
(→ S. 173)):
Possible values
TRUE
FB is enabled
FALSE
FB is disabled
Master_1
AS-i master 1
Master_2
AS-i master 2
Variable must be declared!