SICAM
Fault Sensor Indicator
V2.0 B-Sensor
V01.00
Manual
E50417-H8940-C656-A1
Preface
Table of Contents
Delivery
Overview
Getting Started
Device Functions
SICAM FSI Configurator
Technical Data
Type Testing
Maintenance
Troubleshooting
Firmware and Configurator Version
Compatibility with SICAM FSI
SICAM FSI ACSR Cable Types and Diam-
eter
Index
1
2
3
4
5
6
7
8
9
A
B

Advertisement

Table of Contents

Troubleshooting

loading

Summary of Contents for Siemens SICAM V01.00

  • Page 1 Preface Table of Contents Delivery SICAM Overview Fault Sensor Indicator Getting Started V2.0 B-Sensor Device Functions V01.00 SICAM FSI Configurator Technical Data Manual Type Testing Maintenance Troubleshooting Firmware and Configurator Version Compatibility with SICAM FSI SICAM FSI ACSR Cable Types and Diam- eter Index E50417-H8940-C656-A1...
  • Page 2 Document version: E50417-H8940-C656-A1.00 Trademarks Edition: 08.2023 SIPROTEC, DIGSI, SIGRA, SIGUARD, SIMEAS, SAFIR, SICAM, Version of the product described: V01.00 and MindSphere are trademarks of Siemens. Any unauthor- ized use is prohibited.
  • Page 3: Preface

    (RoHS Direc- tive 2011/65/EU). This conformity has been proved by tests conducted by Siemens AG in accordance of the Council Directive in accordance with the product standard IEC/EN 61326-1 for the EMC directives, and with the standard IEC/EN 61010-1 for the low-voltage directive.
  • Page 4 Preface NOTE Any changes or modifications not expressly approved by the party responsible for compliance could void the users’ authority to operate this equipment. CAUTION Radiation RF exposure This equipment complies with FCC part 15 subpart B radiation exposure limits set forth for an uncontrolled environment.
  • Page 5 Tel.: +49 911 2155 4466 Customer Support Center E-Mail: energy.automation@siemens.com Additional Support For questions about the system, contact your Siemens sales partner. Training Courses Inquiries regarding individual training courses should be addressed to our Training Center: Siemens AG Siemens Power Academy TD Phone: +49 911 9582 7100 Humboldtstraße 59...
  • Page 6 The equipment (device, module) may be used only for such applications as set out in the catalogs and the technical description, and only in combination with third-party equipment recommended and approved by Siemens. Problem-free and safe operation of the product depends on the following: •...
  • Page 7 Preface Symbol Beschreibung Caution, risk of electric shock Caution, risk of danger, ISO 7000, 0434 Guideline 2002/96/EC for electrical and electronic devices Guideline for the Eurasian market Mandatory conformity mark for electronics and electrotechnical products in Morocco OpenSSL This product includes software developed by the OpenSSL Project for use in OpenSSL Toolkit (http:// www.openssl.org/).
  • Page 8 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 9: Table Of Contents

    Table of Contents Preface................................3 Delivery...............................13 Delivery..........................14 Overview..............................15 SICAM Fault Sensor Indicator (FSI) V2.0 B-Sensor...............16 Features and Benefits......................17 Ordering Information......................19 Getting Started............................21 Inspecting the Delivery......................22 Dimensional drawings.......................23 Installation........................24 3.3.1 Installation........................24 SICAM FSI Mounting......................26 3.4.1 SICAM FSI B-Sensor Mounting Methods................26 3.4.2 Mounting SICAM FSI using Hot Stick with Shotgun............
  • Page 10 Table of Contents 4.10 SICAM FSI LED Flashing Sequence..................66 4.11 Low Temperature Cutoff....................67 SICAM FSI Configurator..........................69 Overview.......................... 70 Computer Configuration Requirements ................71 Configurator Installation....................72 5.3.1 SICAM FSI Configurator Installation................72 5.3.2 Installing USB Cable Drivers..................74 5.3.3 Launching the SICAM FSI Configurator.................
  • Page 11 Table of Contents Index.................................135 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 12 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 13: Delivery

    Delivery Delivery SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 14: Delivery

    Delivery 1.1 Delivery Delivery Delivery Note SICAM FSI V2.0 B-sensor is delivered in a cardboard box printed with Siemens logo. Contents of Delivery The scope of delivery are: • 1 SICAM FSI V2.0 B-Sensor according to ordering information • 1 product information WARNING Danger of explosion of the battery.
  • Page 15: Overview

    Overview SICAM Fault Sensor Indicator (FSI) V2.0 B-Sensor Features and Benefits Ordering Information SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 16: Sicam Fault Sensor Indicator (Fsi) V2.0 B-Sensor

    SICAM Fault Sensor Indicator (FSI) V2.0 B-Sensor is developed using the latest hardware technology and is a member of the Siemens SICAM short-circuit indicator product family. The device is used to improve the reliability and to reduce the downtime on the MV overhead distribution grid.
  • Page 17: Features And Benefits

    Overview 2.2 Features and Benefits Features and Benefits Features The salient features of the SICAM FSI V2.0 B-Sensor are: Multiple settings available for fault detection • Threshold settings, auto-threshold, and di/dt settings. • The device offers various configurable options to detect overcurrent faults, including magnitude selec- tion, auto-threshold selection, and monitoring the rate of change of current (di/dt).
  • Page 18 Overview 2.2 Features and Benefits Safe mounting • Safely mountable on the MV overhead line by using a hot stick with shotgun or hot stick (telescopic) with device adaptor. Long range fault indication visibility • Fault localization becomes easier with the device's 6 high luminous red LEDs, which offers visibility for: –...
  • Page 19: Ordering Information

    Overview 2.3 Ordering Information Ordering Information Ordering Information – SICAM FSI V2.0 B-Sensor Table 2-1 SICAM FSI V2.0 B-Sensor Selection and Ordering Data Description Versions Order no. 6 M D 2 3 1 4 - 2 B □ □ 0 ▲...
  • Page 20 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 21: Getting Started

    Getting Started Inspecting the Delivery Dimensional drawings Installation SICAM FSI Mounting Commissioning SICAM FSI B-Sensor Unmounting Updating the Device Firmware SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 22: Inspecting The Delivery

    Getting Started 3.1 Inspecting the Delivery Inspecting the Delivery Inspecting the Delivery After unpacking, first check that all the necessary and ordered items are enclosed as per Contents of Delivery, Page 14. Then inspect the device visually for any mechanical damage. NOTE If the device has been damaged during transport, do not connect and operate it.
  • Page 23: Dimensional Drawings

    Getting Started 3.2 Dimensional drawings Dimensional drawings Device Dimensions The following figure shows the dimensional drawings and different views of SICAM FSI B-Sensor. [dw_fsibsensordimensions, 1, en_US] Figure 3-1 Device Dimensions SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 24: Installation

    Getting Started 3.3 Installation Installation Installation 3.3.1 Preparing the Device for Mounting Before mounting the device on the MV overhead line, proceed as follows: [dw_closedUSBcover, 1, en_US] Figure 3-2 Location of USB Cover on Device Housing [dw_USBcover_procedure, 1, en_US] Figure 3-3 Battery Switch Activation Process •...
  • Page 25 – Cable type (default value: non-insulated) • Siemens recommends to use SICAM FSI Configurator (V3.03 and higher) for device configuration. Refer 5 SICAM FSI Configurator for detailed procedure on device configuration of above parameters, basic and advanced parameters as per customer requirements.
  • Page 26: Sicam Fsi Mounting

    ² to use sunshields while working in bright sunny environment. Siemens recommends using the hot stick with shotgun (Make: Ritz, Cat.No. RC403-0295 or equiv- ² alent) with a minimum isolation of 125 kV AC. Follow safety measures and recommended mainte- nance procedures as per the hot stick with shotgun supplier.
  • Page 27 Getting Started 3.4 SICAM FSI Mounting • Assign 1 device per phase. • Open both hooks of the device. [le_sfsi_hookopen, 1, --_--] Figure 3-4 Opening the Hooks of the Device Hooks CAUTION Exercise caution with the hooks of the device Non-observance of the safety notes may lead to severe injury.
  • Page 28 Getting Started 3.4 SICAM FSI Mounting • Press the hand grip of the hot stick with shotgun and move upwards to open the jaw hook. Attach the device to the hot stick on the eye hook provided on the transparent cover. [le_fsi_hotstickhook, 1, --_--] Figure 3-5 Device Eye Hook Attached to Hot Stick with Shotgun...
  • Page 29 Getting Started 3.4 SICAM FSI Mounting • Press the hand grip of the hot stick with shotgun and move downwards to close the jaw hook. Attach the device to the hot stick on the eye hook provided on the transparent cover. [dw_fsi_devclose, 1, en_US] Figure 3-7 Closing the Jaw Hook of the Hot Stick with Shotgun...
  • Page 30 Getting Started 3.4 SICAM FSI Mounting • The device is ready for mounting on the MV overhead line. Raise the device ensuring that the MV overhead line is positioned between the open clamps arrangement [le_fsi_installine, 1, en_US] Figure 3-9 Device Attached to the MV Overhead Line MV overhead line Clamp SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual...
  • Page 31 Getting Started 3.4 SICAM FSI Mounting • Thrust the device against the MV overhead line until the mounting clamps snaps to the MV overhead line. • In order to confirm the proper snapping of the clamps, exert a slight pull to the device on the MV overhead line.
  • Page 32: Mounting Sicam Fsi Using Hot Stick (Telescopic) With Device Adaptor

    Before mounting the device, ensure that you wear safety helmet, gloves and boots. It is recommended ² to use sunshields while working in bright sunny environment. Siemens recommends using the telescopic hot stick (Make: Ritz, VTT-1/9 or equivalent) with a ² minimum isolation of 125 kV AC. Follow safety measures and recommended maintenance proce- dures as per the hot stick (telescopic) supplier.
  • Page 33 Getting Started 3.4 SICAM FSI Mounting CAUTION Exercise caution with the hooks of the device Non-observance of the safety notes may lead to severe injury. When handling the hooks, exercise caution to avoid any physical harm to the fingers. ² After opening the hooks, do not place your fingers in the hooks to avoid any accidental closure of ²...
  • Page 34 Getting Started 3.4 SICAM FSI Mounting • Remove the rubber fastening from the telescopic hot stick. [le_sfsi_telhotrubber, 1, --_--] Figure 3-13 Removing the Rubber Fastening Rubber fastening Telescopic hot stick SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 35 Getting Started 3.4 SICAM FSI Mounting • Loosen the wing bolt of the telescopic hot stick. [le_sfsi_telhotwingbolt, 1, --_--] Figure 3-14 Loosen the Wing Bolt of the Telescopic Hot Stick Wing bolt Washers (optional) NOTE Do not completely remove the wing bolt from the telescopic hot stick. Washer/s are only used to achieve better grip between wing bolt and device adaptor.
  • Page 36 Getting Started 3.4 SICAM FSI Mounting • Mount the device adaptor on the telescopic hot stick. Make sure that the device adaptor is mounted at the right angles to the telescopic hot stick. [le_sfsi_telhotdevadap, 1, --_--] Figure 3-15 Mounting Device Adaptor on the Telescopic Hot Stick Device adaptor Bottom flange of device adaptor Telescopic hot stick...
  • Page 37 Getting Started 3.4 SICAM FSI Mounting • Match the device adaptor square holes on the telescopic hot stick teeth, so that they fit in place. [le_sfsi_devadapsquthruholes, 1, --_--] Figure 3-17 Matching Device Adaptor Square Holes on the Telescopic Hot Stick Device adaptor square holes Telescopic hot stick teeth •...
  • Page 38 Getting Started 3.4 SICAM FSI Mounting • Place the SICAM FSI in 4 slots of the device adaptor as shown below. [dw_sfsi_devadap3slots, 1, --_--] Figure 3-19 Placing the SICAM FSI in Device Adaptor 4 Slots 4 slots of device adaptor •...
  • Page 39 Getting Started 3.4 SICAM FSI Mounting • To attain preferred height, the telescopic hot stick must be extended and retracted vertically, with the base resting on the ground. Extend the telescopic hot stick sections that are necessary to focus on the estimated height to be reached.
  • Page 40 Getting Started 3.4 SICAM FSI Mounting • Each section of the telescopic hot stick can be extended or retracted with integrated locking button. Extend the top section first until it locks. Extend the subsequent sections likewise and make sure that the integrated buttons are locked until it reaches the necessary height.
  • Page 41 Getting Started 3.4 SICAM FSI Mounting • To retract the stick extensions, maintain the telescopic hot stick in vertical position, place it on the ground. Press the base section button, holding the subsequent section, allowing a smooth sliding down. Proceed likewise to retract the subsequent sections, until the stick is fully retracted. [dw_sfsi_telhotretract, 1, --_--] Figure 3-23 Retracting Subsequent Sections and First Section...
  • Page 42 Getting Started 3.4 SICAM FSI Mounting • The device is now ready for mounting on the MV overhead line. Raise the device ensuring that the MV overhead line is positioned between the open clamps arrangement. [dw_sfsi_telhotmountdevice, 1, --_--] Figure 3-25 Mounting SICAM FSI on MV Overhead Line •...
  • Page 43 Getting Started 3.4 SICAM FSI Mounting • Turn the telescopic hot stick along with device adaptor until SICAM FSI flanges align with device adaptor cut sections at 4 locations. [dw_sfsi_deviceunlock, 1, --_--] Figure 3-26 Unlocking the Device Adaptor from SICAM FSI •...
  • Page 44 Getting Started 3.4 SICAM FSI Mounting NOTE Before the telescopic hot stick is lowered, the orientation of SICAM FSI must be aligned as shown in Figure 3-27 and ensure that device transparent cover is always facing towards the ground. SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 45: Commissioning

    Getting Started 3.5 Commissioning Commissioning SICAM FSI V2.0 B-Sensor Commissioning 3.5.1 Visual indication for voltage presence on a line will be seen only once when the device has been mounted on the line after it has been magnetically reset. Magnetic reset can be done by touching the magnet adaptor to the device transparent cover for approximately 1 s.
  • Page 46 Getting Started 3.5 Commissioning [le_fsi_magnetreset_tel, 1, en_US] Figure 3-29 Reseting the Device using Magnet Adaptor using Telescopic Hot Stick Transparent cover Magnet adaptor Telescopic hot stick NOTE The magnetic reset of the device can be performed before mounting or after mounting on the overhead line.
  • Page 47: Sicam Fsi B-Sensor Unmounting

    Getting Started 3.6 SICAM FSI B-Sensor Unmounting SICAM FSI B-Sensor Unmounting SICAM FSI B-Sensor may be unmounted from the MV overhead line in the following situations: • When the device is faulty • To replace the battery • When the device firmware update is required Before unmounting SICAM FSI, refer to 3.4 SICAM FSI Mounting for safety instructions.
  • Page 48 Getting Started 3.6 SICAM FSI B-Sensor Unmounting [le_sfsi_telhotstkgrndwoFSIv2, 1, --_--] Figure 3-31 Telescopic Hot Stick Base Resting on the Ground and Aligning Device Adaptor For more information about extending and retracting telescopic hot stick vertically, refer to 3.4.3 Mounting SICAM FSI using Hot Stick (Telescopic) with Device Adaptor.
  • Page 49 Getting Started 3.6 SICAM FSI B-Sensor Unmounting Turn the device adaptor with the telescopic hot stick in either direction to lock the SICAM FSI in the ² device adaptor. [dw_sfsiv2_unmountdevicelck, 1, --_--] Figure 3-33 Locking the SICAM FSI in Device Adaptor Move the telescopic hot stick approximately 2 m in parallel to the MV overhead line to release the device.
  • Page 50: Updating The Device Firmware

    • You can also contact local Siemens office or contact customer support for latest SICAM FSI V2.0 B-Sensor firmware and SICAM FSI Configurator files. You can update the device firmware via USB Type-C cable with SICAM FSI Configurator (version 3.03 and...
  • Page 51: Device Functions

    Device Functions Voltage Detection and Network Parameters Fault Detection Permanent-Fault Verification Time (PFVT) Temporary/Permanent Fault Fault Resets Inrush Restraint Auto-Reclosure Self Test Battery Health 4.10 SICAM FSI LED Flashing Sequence 4.11 Low Temperature Cutoff SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 52: Voltage Detection And Network Parameters

    Device Functions 4.1 Voltage Detection and Network Parameters Voltage Detection and Network Parameters Voltage Detection 4.1.1 SICAM FSI V2.0 B-Sensor senses the presence/absence of MV overhead line voltage. In case of a fault condition, the voltage absence or presence is used to determine whether the fault is a temporary fault or permanent fault.
  • Page 53: Fault Detection

    Device Functions 4.2 Fault Detection Fault Detection The device detects and indicates overcurrent phase and di/dt faults by continuously monitoring the phase current based on the device configuration. In a fault condition, the voltage presence or absence is used to determine a temporary fault or permanent fault indication.
  • Page 54 Device Functions 4.2 Fault Detection • Range Change Monitoring Time (T1): This timer is designed to monitor the transition between current ranges when there is a change in the load current. It is activated when the load current crosses the maximum limit of a current range. The purpose of T1 is to track the duration during which the load current remains within the new range.
  • Page 55: Di Fault

    Device Functions 4.2 Fault Detection NOTE By default, the fault current threshold is initially set to 1500 A through the auto threshold functionality. Subsequently, the device actively monitors the load current and adaptively recalibrates the fault current threshold to ensure optimal fault detection and response. NOTE The auto-threshold functionality is deactivated when there is voltage absence detected on the overhead line.
  • Page 56: Permanent-Fault Verification Time (Pfvt)

    Device Functions 4.3 Permanent-Fault Verification Time (PFVT) Permanent-Fault Verification Time (PFVT) The Permanent-Fault Verification Time (PFVT) is the time range required to convert the temporary fault to a permanent fault, based on status of voltage and current. The PFVT can be configured as Disabled, 3 s, 35 s, and 70 s. For example, if the PFVT is set as 35 s and if a fault (phase, di/dt) occurs, it is termed as temporary fault.
  • Page 57: Temporary/Permanent Fault

    Device Functions 4.4 Temporary/Permanent Fault Temporary/Permanent Fault Phase Faults The phase faults are classified as: • Temporary phase fault • Permanent phase fault Temporary Phase Fault When the phase current exceeds the configured current threshold, the device detects and indicates a tempo- rary phase fault.
  • Page 58 Device Functions 4.4 Temporary/Permanent Fault [dw_sfsi_permfault, 1, en_US] Figure 4-2 Permanent Phase Fault Temporary DI Fault Faults due to current variations can also be indicated by the rate of change of the phase current (di/dt) and it is termed as DI fault. SICAM FSI detects the rate of change of current (di/dt) typically in 2 cycles ±...
  • Page 59 Device Functions 4.4 Temporary/Permanent Fault [dw_sfsi_tempdidtfault, 1, en_US] Figure 4-3 Temporary di/dt Fault Permanent DI Fault The DI fault evolves from temporary DI fault to permanent DI fault, when the voltage and current drops on the MV overhead line within PFVT. The device indicates the permanent DI fault via LEDs with a flashing pattern of 1 flash every 2 s or 6 s depending on the device variant selected.
  • Page 60 Device Functions 4.4 Temporary/Permanent Fault [dw_sfsi_permdidtfault, 1, en_US] Figure 4-4 Permanent DI Fault SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 61: Fault Resets

    Device Functions 4.5 Fault Resets Fault Resets After the fault is reset, the device LEDs stops flashing and the phase-current measurements start again and the device is ready for detecting the new faults. The faults detected by the device can be reset with the following methods.
  • Page 62: Inrush Restraint

    Device Functions 4.6 Inrush Restraint Inrush Restraint During the voltage restoration on the MV overhead line, the device blocks the detection of faults due to the transformer magnetization within the configured inrush-restraint time. The inrush-restraint time can be configured as Disabled, 3 s, 30 s, and 60 s. The inrush-restraint time is initiated only after a voltage is detected in SICAM FSI.
  • Page 63: Auto-Reclosure

    Device Functions 4.7 Auto-Reclosure Auto-Reclosure The auto-reclosure function is used to block the redundant fault detection during the auto-reclosure retries which are made to restore the MV overhead line. In such case, when auto-reclosure time is set in the SICAM FSI Configurator, the device blocks such redundant fault detection for the configured auto-reclosure time.
  • Page 64: Self Test

    Device Functions 4.8 Self Test Self Test You can execute the self test by magnet reset to verify the health of the device. During the self test, the device checks the status of the following: • Battery health The success of self test is indicated by the magnetic reset LED sequence. The failure of battery is indicated by a specific LED flashing pattern.
  • Page 65: Battery Health

    3 board LEDs every 15 s. If the battery voltage is low, Siemens recommends replacing the batteries with new ones within 1 month after appearance of the low-battery indication.
  • Page 66: Sicam Fsi Led Flashing Sequence

    Device Functions 4.10 SICAM FSI LED Flashing Sequence 4.10 SICAM FSI LED Flashing Sequence The device has 12 high luminous red LEDs for indicating events. • 6 dome LEDs utilised for fault indication • 6 board LEDs (2 sets of 3 LEDs each) utilised for other events The fault is visible in 360 degrees and the visibility ranges from 400 m in day and 800 m at night.
  • Page 67: Low Temperature Cutoff

    Device Functions 4.11 Low Temperature Cutoff 4.11 Low Temperature Cutoff SICAM FSI is built in with an automatic cutoff feature when the temperature falls below -40 °C . The device functionality will get disabled when the temperature falls below -40 °C and will get re-enabled when the temperature goes above -37 °C.
  • Page 68 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 69: Sicam Fsi Configurator

    SICAM FSI Configurator Overview Computer Configuration Requirements Configurator Installation Control Functions Starting the SICAM FSI Configurator User Interface Dashboard Basic Parameter Settings Advanced Parameter Settings Device Info 5.10 Device Settings 5.11 Log off 5.12 SICAM FSI Configurator Uninstallation SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 70: Overview

    SICAM FSI Configurator 5.1 Overview Overview SICAM FSI Configurator is a Web-browser based configurator which allows you to configure and apply the parameters to the SICAM FSI V2.0 B-Sensor device. The main functions of SICAM FSI Configurator are: • Configure and apply the engineering parameter settings to the device •...
  • Page 71: Computer Configuration Requirements

    SICAM FSI Configurator 5.2 Computer Configuration Requirements Computer Configuration Requirements Before installing and operating the SICAM FSI Configurator, ensure that your personal computer (PC) or laptop computer is equipped with the following minimum hardware specifications and the operating system: • 1-GHz processor or higher •...
  • Page 72: Configurator Installation

    SICAM FSI Configurator Setup – Welcome Screen Click Next > to install the SICAM FSI Configurator in the destination folder. ² Siemens recommends keeping the SICAM FSI Configurator installation in the following default folder: C:\Program Files (x86)\Siemens Energy\SICAM FSI\ SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual...
  • Page 73 SICAM FSI Configurator 5.3 Configurator Installation [Picture3, 1, --_--] Figure 5-2 SICAM FSI Configurator Setup – Destination Folder Click Next > to begin the SICAM FSI Configurator installation. ² [Picture4, 1, --_--] Figure 5-3 SICAM FSI Configurator Setup – Ready to Install Click Install to start the SICAM FSI Configurator installation.
  • Page 74: Installing Usb Cable Drivers

    SICAM FSI Configurator Setup – Installation In Progress [Picture6, 1, --_--] Figure 5-5 SICAM FSI Configurator Setup – Installation Finished Click Finish to complete the Siemens FSI Configurator installation. ² Installing USB Cable Drivers 5.3.2 If you are installing the SICAM FSI Configurator for the first time, install the USB drivers on your PC or laptop computer.
  • Page 75 SICAM FSI Configurator 5.3 Configurator Installation Plug in the USB connector to the USB port of the PC or laptop computer. ² Magnetic reset of the device is performed. ² For more information about magnetic reset, refer to 3.5.1 SICAM FSI V2.0 B-Sensor Commissioning.
  • Page 76 SICAM FSI Configurator 5.3 Configurator Installation [sc_fsi_usbdri-updatedriver, 1, --_--] Figure 5-7 UART Cable Drivers – Update Driver Software Click Browse my computer for drivers to locate and install the driver software. ² SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 77 Figure 5-8 USB Cable Drivers – Locate Driver Software The drivers are available in the following default folder: ² C:\Program Files (x86)\Siemens Energy\SICAM FSI Click Next to begin the driver installation. ² SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 78 SICAM FSI Configurator 5.3 Configurator Installation [sc_fsi_usbdri-next, 1, --_--] Figure 5-9 USB Cable Drivers – Driver Installation SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 79 SICAM FSI Configurator 5.3 Configurator Installation [sc_fsi_usbdri-instprog, 1, --_--] Figure 5-10 USB Cable Drivers – Installation In Progress Click Close once the driver software is successfully installed. ² SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 80 SICAM FSI Configurator 5.3 Configurator Installation [sc_fsi_usbdri-success, 1, --_--] Figure 5-11 USB Cable Drivers – Installation Finished Once the SICAM FSI drivers are successfully installed, make sure that the CP210x USB To UART Bridge is ² visible in Device Manager → Ports. SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 81: Launching The Sicam Fsi Configurator

    To launch the SICAM FSI Configurator after the installation, proceed as follows: Double-click the SICAM FSI Configurator icon from the desktop to open the SICAM FSI Configurator. ² - or - Select the Start Menu → All Programs → Siemens Energy → FSI Web Configurator. ² [sc_fsi_launchicon_20160411, 1, en_US] 5.3.3...
  • Page 82 Search SICAM FSI in search bar and click on the SICAM FSI Configurator icon. ² - or - Select the Start Menu → All Programs → Siemens Energy → FSI Web Configurator. ² [sc_fsi_launchicon_, 1, en_US] SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual...
  • Page 83: Control Functions

    SICAM FSI Configurator 5.4 Control Functions Control Functions Control Elements and Control Functions The following table lists the control elements and control functions. Table 5-1 Control Elements and Control Functions Control Elements Control Functions Home screen Backup device settings Reset to factory settings Restore device settings Update firmware Log off...
  • Page 84: Starting The Sicam Fsi Configurator User Interface

    • Mozilla Firefox 45.0 or higher NOTE Siemens recommends using Google Chrome 10.0 or higher. Before starting the SICAM FSI Configurator user interface, the following preconditions must be satisfied: • If the SICAM FSI is used for first time, complete the installation procedure.
  • Page 85 SICAM FSI Configurator 5.5 Starting the SICAM FSI Configurator User Interface The Log-on to device dialog appears. [sc_sfsi_configlogon, 1, --_--] Figure 5-14 Log-on to Device Dialog Click OK to log on to the SICAM FSI Configurator. ² The Device Information and Settings tiles page appears. SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 86: Dashboard

    SICAM FSI Configurator 5.6 Dashboard Dashboard SICAM FSI Configurator Dashboard 5.6.1 Based on the selected COM port, you can connect and log on to the SICAM FSI Configurator. After successful log on, the Dashboard page appears and contains the following pages: •...
  • Page 87: Settings

    SICAM FSI Configurator 5.6 Dashboard [Picture9, 1, --_--] Figure 5-16 Device Information Settings 5.6.3 The settings page displays the following parameters in a tree view structure: • Basic parameters • Advance parameters • Device info [Picture10, 1, --_--] Figure 5-17 SICAM FSI Configurator - Settings (Engineering) SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 88: Basic Parameter Settings

    SICAM FSI Configurator 5.7 Basic Parameter Settings Basic Parameter Settings To set the basic parameters, proceed as follows: • In the SICAM FSI Configurator dashboard, navigate to Settings → Basic Parameters. [4, 1, --_--] Figure 5-18 Basic Parameter Settings Basic Parameter Settings Setting Value Power frequency 50 Hz or 60 Hz...
  • Page 89 SICAM FSI Configurator 5.7 Basic Parameter Settings Information Section The information section provides you more information about the parameters and the settings range when you are configuring the parameters. To find more information about the parameters, proceed as follows: • Click the arrow sign ◀...
  • Page 90: Advanced Parameter Settings

    SICAM FSI Configurator 5.8 Advanced Parameter Settings Advanced Parameter Settings SICAM FSI Configurator user interface allows you to set the following advanced device parameters: • Inrush restraint time • Cable type and diameter • Auto reclosure • Phase fault indication •...
  • Page 91 The battery-low indication is displayed when the battery voltage level falls below 3.08 V. Siemens recommends replacing the battery with a new one within 1 month after appearance of the low-battery indication.
  • Page 92: Device Info

    SICAM FSI Configurator 5.9 Device Info Device Info The device information page displays the following information: • Year of manufacturing • MLFB • Serial number • Device ID • Hardware version In the SICAM FSI dashboard, navigate to Settings → Device Info. ²...
  • Page 93: Device Settings

    Backup device settings allows you to save the configured device settings in the PC or laptop computer. Siemens recommends creating a backup of the device settings. The backup settings can be used to view configuration data via SICAM FSI Configurator and restore the device settings.
  • Page 94 SICAM FSI Configurator 5.10 Device Settings [sc_fsib-sensor_config_backup, 1, --_--] Figure 5-23 Backup Device Settings The Backup device settings dialog appears. [Picture15, 1, --_--] Figure 5-24 Backup Device Settings Dialog Click ✓ to download the the backup device settings file as shown below: ²...
  • Page 95: Restore Device Settings

    SICAM FSI Configurator 5.10 Device Settings [Picture16, 1, --_--] Figure 5-25 Backup File - Download Complete Restore Device Settings 5.10.3 Restore device settings allows the device to restore the device settings from the saved backup file. This backup file can also be used to configure the new device in the field, if the device parameters are to be same. To restore the device settings, proceed as follows: In the SICAM FSI Configurator dashboard, click the Open menu and select Restore device settings..
  • Page 96 SICAM FSI Configurator 5.10 Device Settings [Picture17, 1, --_--] Figure 5-27 Restore Device Settings Dialog Click Select a file. ² Select the valid device settings backup (*.xml) file, for example, SetupConfig.xml. ² [sc_fsi_restoredevicesetselectfile, 1, --_--] Figure 5-28 Valid Backup-File Selection Click Open.
  • Page 97 SICAM FSI Configurator 5.10 Device Settings [Picture18, 1, --_--] Figure 5-29 Restore Device Settings Backup File Click ✓. ² The device settings are restored from the selected file and the message Finished successfully. A log-on is required! appears. [sc_fsi_restdevsucc_20160411, 2, en_US] Figure 5-30 Device Settings Restored Successfully SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual...
  • Page 98: Updating Firmware

    You can download and update the latest firmware to the SICAM FSI device. Before updating the SICAM FSI firmware (for example, FSI_V01.00.fw) on the PC or laptop computer, down- load the SICAM FSI firmware. Contact local Siemens office or contact customer support for latest SICAM FSI firmware.
  • Page 99 SICAM FSI Configurator 5.10 Device Settings [Picture20, 1, --_--] Figure 5-33 Firmware File Update Dialog Click Select a file. ² The Choose File to Upload dialog appears. [sc_fsi_updatefwselectfile, 1, en_US] Figure 5-34 Choose File to Upload Dialog Select the valid firmware file, for example, FSI_V01.00.fw. ²...
  • Page 100 SICAM FSI Configurator 5.10 Device Settings [Picture22, 1, --_--] Figure 5-35 Firmware File Update Dialog Click ✓. ² The Update firmware dialog appears. [Picture23, 1, --_--] Figure 5-36 Firmware Upload in Progress After successful firmware update, the message Finished successfully. A log-on is required! appears. ²...
  • Page 101 SICAM FSI Configurator 5.10 Device Settings [Picture24, 1, --_--] Figure 5-37 Firmware File Update Successful Click ✓ to Close. ² After the successful firmware download, the device restarts. SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 102: Log Off

    SICAM FSI Configurator 5.11 Log off 5.11 Log off Log off allows you to end the user session of the SICAM FSI Configurator. To log off from the SICAM FSI Configurator, proceed as follows: In the SICAM FSI Configurator dashboard, click the Open menu and select Log off to disconnect from the ²...
  • Page 103: Sicam Fsi Configurator Uninstallation

    ² The Programs and Features window is displayed [26a, 1, --_--] Figure 5-39 Uninstalling Program Right-click Siemens SICAM FSI and select theUninstall option from the context menu. ² [Picture27, 1, --_--] Figure 5-40 SICAM FSI Configurator – Setup Uninstallation Click Next >.
  • Page 104 Click Remove to start the uninstallation process. ² The SICAM FSI Configurator program is removed from your computer. This process can take several minutes. Click Finish to complete the Siemens SICAM FSI Configurator uninstallation. ² SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 105 SICAM FSI Configurator – Setup Uninstallation Finished Uninstallation via the Start Menu To uninstall the SICAM FSI Configurator via the start menu, proceed as follows: Select theStart Menu → All Programs → Siemens Energy → FSI Web Configurator → Uninstall. ² [sc_fsi_configuninstall, 1, --_--] Figure 5-44 SICAM FSI Configurator –...
  • Page 106 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 107: Technical Data

    Technical Data Application Data Rated voltage (V 6.6 kV, 11 kV, 12.5 kV, 13.8 kV, 22 kV, 25 kV, 33 kV, 34.5 kV, 44 rated kV, 45 kV, 66 kV, and 69 kV Maximum operating voltage 83 kV Maximum operating current 1500 A Maximum continuous operating current 800 A...
  • Page 108 Technical Data Range change memorize time (T2) 0 s to 120 s (steps of 30 s) DI current 5 A to 80 A (steps of 5 A), 120 A, 160 A Starting from 10 A phase current Fault-indication time B-Sensor Type 1: 2 h to 16 h (steps of 1 h) B-Sensor Type 2: 2 h to 4 h (steps of 1 h) Permanent-fault verification time 3 s, 35 s, and 70 s...
  • Page 109: Type Testing

    Type Testing This section describes about the type testing performed on SICAM FSI V2.0 B-Sensor according to IEC 61326-1, IEC 62689-1, and IEC 61010-1. EMI/EMC Tests Environmental Tests Mechanical Tests Electrical Tests Safety Tests SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 110: Emi/Emc Tests

    Type Testing 7.1 EMI/EMC Tests EMI/EMC Tests Table 7-1 EMI/EMC Tests Test Reference Standard Test Requirement Electrostatic discharge test IEC 62689-1, Table 16 Severity class 3 IEC 61000-4-2 6 kV contact discharge, 8 kV air discharge IEC 61326-1 Power frequency magnetic IEC 62689-1, Table 16 Severity class 4 field immunity 50 Hz/60 Hz...
  • Page 111: Environmental Tests

    Type Testing 7.2 Environmental Tests Environmental Tests Table 7-2 Environmental Tests Test Reference Standard Test Requirement Dry heat test IEC 62689-1 +75 °C IEC 60068-2-2 Duration: 16 h with device turned OFF 16 h with device turned ON IEC 60068-2-2 (+85 ±2) °C Dry heat test (storage) Duration: 16 h...
  • Page 112: Mechanical Tests

    Type Testing 7.3 Mechanical Tests Mechanical Tests Table 7-3 Mechanical Tests Test Reference Standard Test Requirement Vibration response test (sinusoidal) IEC 62689-1 Frequency: 10 Hz to 500 Hz IEC 60068-2-6 10 m/s amplitude 0.075 mm, 23 min Sweep rate: 1 oct./min Number of sweep cycles: 2/axis in 3 directions Bump test...
  • Page 113: Electrical Tests

    Type Testing 7.4 Electrical Tests Electrical Tests Table 7-4 Electrical Tests Test Reference Standard Test Requirement Dielectric withstand IEC/EN 61010-1 125 kV with the help of hotstick Overvoltage IEC/EN 61010-1 Category IV Degree of pollution IEC/EN 61010-1 Category 2 Maximum altitude above sea level IEC/EN 61010-1 5000 m Short-circuit current withstand test IEC 62689-1...
  • Page 114: Safety Tests

    Type Testing 7.5 Safety Tests Safety Tests Table 7-5 Safety Tests Test Reference Standard Test Requirement Product safety test EN/IEC 61010-1 Tests as per clause no. 4 Marking and documentation as per clause no. Protection against electric shock as per clause no.
  • Page 115: Maintenance

    Maintenance Environmental Protection Hints Battery Replacement SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 116: Environmental Protection Hints

    When disposing of or transferring a mobile storage device, Siemens strongly recommends physically destroying it or completely deleting data from the mobile storage device by using a commercially available computer data erasing software.
  • Page 117: Battery Replacement

    Battery Replacement The device uses non-rechargeable 3.6 V Lithium-thionyl chloride batteries. Siemens recommends replacing the battery within 1 month after appearance of the low-battery indication. NOTE It is mandatory to replace the battery with Make: Eve Energy, ER34615+SPC1550 hybrid battery, part number: G0962-LF (Article Number: 6MD2318 - 4BB01) to claim the required battery life.
  • Page 118 Maintenance 8.2 Battery Replacement • Disconnect the following existing connections from the PCBA – Disconnect the CT cable from 3-pin X5 connector and voltage detection plate wire from Y1 stub on the PCBA. [le_sfsi_batrep_x5, 1, --_--] Figure 8-1 Connections at X5 Connector and Y1 Stub CT cable at X5 connector voltage detection plate wire at Y1 stub –...
  • Page 119 Maintenance 8.2 Battery Replacement • Remove the battery cover by unscrewing the 3 M3 screws (using torque: 0.5 Nm) using a Phillips screwdriver of tip size 1. Take out the old batteries from the device [le_sfsi_batrep_removebat, 1, --_--] Figure 8-3 Removal of Battery Cover and Old Batteries •...
  • Page 120 Maintenance 8.2 Battery Replacement • Place the battery cover again in the housing and tighten the 3 M3 screws. Alignement Tip: Use the reference arrows affixed on the battery cover and device housing for aligning the battery cover (reference position: both arrows must be in a straight line). Tighten the M3 screws into the threaded hole in the device housing for smooth alignment.
  • Page 121 Maintenance 8.2 Battery Replacement • Place the PCBA in the housing such that 3 mounting bosses of the housing is locked into the assembly holes of the PCBA. [le_sfsi_batrep_pcbaaligned, 1, --_--] Figure 8-7 PCBA Aligned with the device housing • Align the transparent cover with the sealing hole.
  • Page 122 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 123: Troubleshooting

    Troubleshooting Troubleshooting Device Return - Shipping Instructions SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 124: Troubleshooting

    If this is not sucessfull, update the USB cable drivers via Control Panel → Device Manager and browse for the USB drivers from the following path: C:\Program Files (x86)\Siemens Energy\SICAM FSI Refer to 5.3.2 Installing USB Cable Drivers for infor- mation on USB cable drivers installation and verifica- tion.
  • Page 125 Troubleshooting 9.1 Troubleshooting Observations Action If there is no visual indication for fault condition in The device does not indicate any fault condition only the device when the battery is drained. To confirm the battery drained condition: • Perform magnetic reset and check for the LED flashing sequence.
  • Page 126 Troubleshooting 9.1 Troubleshooting If the above troubleshooting checklist does not help in correcting the problem, contact the local Siemens office or contact customer support. Our customer support center provides a 24-hour service. Siemens AG Smart Infrastructure – Digital Grid Customer Support Center Phone: +49 911 2155 4466 E-Mail: energy.automation@siemens.com...
  • Page 127: Device Return - Shipping Instructions

    9.2 Device Return - Shipping Instructions Device Return - Shipping Instructions In the event of shipping the SICAM FSI V2.0 B-Sensor back to Siemens factory or any Siemens locations, follow instructions from customer support and also mandatory procedure below. Note the device serial number for future reference. Refer to label on the housing for device serial number.
  • Page 128 Troubleshooting 9.2 Device Return - Shipping Instructions • Measure the battery voltage across the terminals on the PCBA with a multimeter as shown in Figure 9-2. – If the battery is found healthy (voltage is ≥ 6 V for B-Sensor Type 1 or ≥ 9 V for B-Sensor Type 2), disassemble the battery and then store for future use as per the storage conditions.
  • Page 129 Troubleshooting 9.2 Device Return - Shipping Instructions • Place the transparent cover in the device housing and tighten screws using a torque screw driver. • Repack the SICAM FSI as shown in Figure 9-3. [dw_sfsi_dangdsrepkg, 1, --_--] Figure 9-3 Repacking SICAM FSI and PCBA without Battery NOTE The original packaging of SICAM FSI V2.0 B-Sensor falls under Dangerous Goods Regulations due to the presence of batteries (refer...
  • Page 130 SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 131: A Firmware And Configurator Version Compatibility With Sicam Fsi

    Firmware and Configurator Version Compatibility with SICAM FSI Firmware and Configurator Version Compatibility with SICAM FSI V2.0 B-Sensor SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 132: Firmware And Configurator Version Compatibility With Sicam Fsi V2.0 B-Sensor

    Firmware and Configurator Version Compatibility with SICAM FSI A.1 Firmware and Configurator Version Compatibility with SICAM FSI V2.0 B-Sensor Firmware and Configurator Version Compatibility with SICAM FSI V2.0 B-Sensor Following table provides firmware and configurator version compatibility with SICAM FSIs: Table A-1 Firmware Versions Compatibility MLFB of SICAM FSI V2.0 B-Sensor...
  • Page 133: Bsicam Fsi Acsr Cable Types And Diameter

    SICAM FSI ACSR Cable Types and Diameter Aluminum Conductor Steel Reinforced (ACSR) Cable Type and Diameter SICAM, Fault Sensor Indicator V2.0 B-Sensor, Manual E50417-H8940-C656-A1, Edition 08.2023...
  • Page 134: Aluminum Conductor Steel Reinforced (Acsr) Cable Type And Diameter

    SICAM FSI ACSR Cable Types and Diameter B.1 Aluminum Conductor Steel Reinforced (ACSR) Cable Type and Diameter Aluminum Conductor Steel Reinforced (ACSR) Cable Type and Diameter Following table provides list of ACSR cable types and diameter as per BS 215 standard: ACSR Cable Type Approximate Overall Diameter Rose...
  • Page 135 Index 1,2,3 ... 6MD23 19 Fault detection parameters 107 Fault indication 108 Fault resets 61 Firmware update 50 Front view 23 Advanced parameter settings 90 Application data 107 Auto reset 61 Auto Threshold 53 Information section 89 Inrush restraint 62 Backup device settings 93 Basic parameter settings 88 Battery health 65...
  • Page 136 Index Restore the device settings 95 Settings 86 SICAM FSI configurator settings 87 SICAM FSI Configurator user interface 84 SICAM FSI V2.0 B-Sensor Benefits 17 SICAM FSI V2.0 B-Sensor Features 17 Side view 23 Temporary fault 57 Temporary phase fault 57, 58 Troubleshooting 124 Unmounting 47 Update firmware 98...