Outside Temperature; Connection Choices; Outside Temperature At Terminal - Siemens RMB795B Basic Documentation

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

2 possible signal
sources
4 variants
Settings and
connection
Configuration
Setting values
52 / 144
Siemens
Building Technologies
7.5

Outside temperature

7.5.1

Connection choices

For the outside temperature, the following 2 signal sources can be used:
• Outside air temperature connected locally to the terminal,
activated by the identifier "Outside temperature"
• Outside temperature via bus.
In addition, it is important whether or not "Outside temperature" communication is
active. Hence, the following 4 variants are made available:
Variant
Outside temperature at the
terminal
Communication outside
temperature not active.
Outside temperature at the
terminal
Communication outside
temperature active.
No outside temperature at
terminal.
Communication outside
temperature active.
No outside temperature at
terminal.
Communication outside
temperature not active.
7.5.2

Outside temperature at terminal

Settings and the connection diagram for the outside temperature on the terminal, is
described under Sec. 7.2 "Analog inputs (Xx)".
Main menu > Commissioning > Extra configuration > Input identifier
Op. line
Adjustable values / remarks
...X...
Activate function by assigning the "Outside temperature" value
to the input.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Inputs > ...X...
Op. line
Range
Type
Ni1000, 2xNi1000, T1, Pt1000, DC
0...10 V
Value low
Depending on selected type.
Value high
Depending on selected type.
Correction
− 3.0...+3.0 K
Central control unit RMB795B
Inputs
Diagram
Effect
Central control unit operates with
its own outside temperature.
T
No impact on the bus.
Central control unit operates with
its own outside temperature.
T
Using the bus, the outside
temperature is also delivered to
other devices.
Central control unit operates with
the outside temperature
T
delivered via the bus by some
other controller
Central control unit has no
outside temperature.
T
Factory setting
Ni1000
Depending on type.
Depending on type.
0 K
CE1P3122en
18.01.2012