Data acquisition

15.1

Trend

15.1.1 Connections and application

The following illustration shows the function block connections as shown on the
configuration sheet:
The Trend function block is used for time-related recording of measured values. It
provides 4 independent trend channels.
A trend channel can record one measured value.
Two trend channels can be displayed per Trend view: Primary channel plus extra
channel as a reference.
It is possible to record signals from local inputs of the central control unit RMB795B
as well as room temperatures and outside temperature via bus.

15.1.2 Views

The following illustration shows a 24-hour view on the operator unit with primary
trend curve and reference curve for an extra channel:
The current 24-hour views (8 minutes, 8 hours, 24 hours) show the date and the
current value of the primary trend curve at the top.
The primary trend curve is shown as a solid line, the reference curve as a dotted
line.
The Y-axis label refers to the settings of the primary channel. If the Y-axes of the
two channels do not match, a warning symbol appears below the axis.
Navigation between the 4 different views is made easy with the OK knob of the
operator unit:
• 8-minute view:
Sampling every 5 seconds, last 8 minutes.
• 8-hour view:
Sampling every 5 minutes, last 8 hours.
• 24-hour view:
Sampling every 15 minutes, current day.
• Rolling over the last 6 days: Sampling every 15 minutes, last 6 days.
Comment: The 24-hour view shows the last 6 days.
Central control unit RMB795B
Data acquisition
121 / 144
CE1P3122en
18.01.2012