Siemens RMB795B Basic Documentation page 118

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Device 2
Configuration diagram
Fault status messages
118 / 144
Siemens
Building Technologies
In RMS705B, device 2 (rooftop fan), the following is configured:
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
N.X1
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
N.Q1
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
N.X1
Unit 1
C
Logic 1
In the event an input is to receive as signal from the bus and this signal is
unavailable, the fault message "[...X...] sensor error" is sent after a period expires
(ca. 30 minutes).
No.
Text
5902
>1 identical LTE zone
Central control unit RMB795B
Communication
Range
Digital
Range
2
Range
1
Zone 1
Zone 2
Effect
Non urgent message; must not be
acknowledged.
Factory setting
Factory setting
Factory setting
Unit 2
CE1P3122en
18.01.2012