Distribution Zones" Menu Item; Universal Transmission And Reception Zones - Siemens RMB795B Basic Documentation

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Setting values
Explanations relating to
the setting values
Reference room 1...3
Setting values
Setting values
114 / 144
Siemens
Building Technologies
Main menu > Commissioning > Communication > Room group 1...10 >
Operating line
Holidays/special day
operation
Holidays / special day
zone
The behavior and the zone address for exchange of holiday/special day operation
can be set:
• The setting "Master" means that the central control unit RMB795B sends, at the
beginning of the switching period, and then cyclically at 15-minute intervals, the
holidays/special days operating data via the KNX bus.
• For the setting "Slave", it receives the holidays/special days operating data from
the holidays/special days master.
The slave must be assigned to the same holidays/special days zone.
1 to 3 specially selected individual rooms can be defined as reference rooms,
which are used for calculating the "Night cooling" function (see Sec. 8.9). These
rooms must then be in the same room group (geographical zone.apartment) as
defined for the room group. For this reason, for choosing the reference rooms, it is
not possible to set the Geographical zones apartment, but only the Geographical
zones Room.
Each reference room can be assigned individual text.
Main menu > Commissioning > Communication > Room group 1...10 > Reference room
1...3 >
Operating line
Geographical zone (room)
Reference room 1...3...3

13.2.3 "Distribution zones" menu item

Main menu > Commissioning > Communication > Distribution zones >
Operating line
Outside temperature zone
Refrigeration distribution
zone
refrigeration distribution
zone, generation side
Heat distribution zone
Heat distr zone source
side

13.2.4 Universal transmission and reception zones

The device RMU795B allows for the universal exchange of data via its own
terminals as well as via terminals for the extension module RMZ78x. The data is
exchanged via KNX bus from device to device.
Central control unit RMB795B
Communication
Range
Autonomous, slave,
master.
1...31
Range
---, 1...63
20 characters
Range
----, 1...31
----, 1...31
----, 1...31
----, 1...31
----, 1...31
Factory setting
Room group 1 =
Master, all other room
groups slave
1
Factory setting
---
Factory setting
----
1
----
1
----
CE1P3122en
18.01.2012