Start From The Main Menu; Basic Configuration; Select Basic Type "B - Siemens RMB795B Basic Documentation

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Procedure
Introduction
Selection deletes extra
configuration
Maintained values
New extra configuration
32 / 144
Siemens
Building Technologies
5.2.2

Start from the main menu

To navigate from the main menu to commissioning:
Step
Action
1
To select the Access level
menu, press simultaneously
the OK knob and the ESC
button. Select operating line
Password level and confirm
with the OK knob. Enter the
password (7).
2
Select and confirm operating
line Commissioning with the
OK knob
3
Press the OK knob a second
time
5.3

Basic configuration

The Basic configuration menu is used to make the following settings:
• Selecting basic type "B"
• Assign the central control unit position to the connected extension modules
5.3.1

Select basic type "B"

On the RMB795B central control unit, an empty "Basic configuration" is filed. If
selected, all configurations of the extra configuration will be deleted (for
connections, refer to the configuration diagram).
When selecting a new, empty basic configuration, the following values will not be
deleted:
• All user-defined texts and business cards.
• Calendar and time switch room group settings.
• Basic settings on the Communication menu.
• Current time of day.
• Trend settings.
• Values on the Settings > Device menu
After selecting basic type "B", a start can be made with a new configuration on the
Extra configuration menu.
Central control unit RMB795B
Commissioning
Result
The password level is active.
On the device side:
• The application (communication) is
stopped
• All outputs are set to a defined OFF
state.
On the display:
• The Commissioning menu is
displayed.
CE1P3122en