Setting And Resetting Meter Readings; Display Meter Readings; Assign Texts - Siemens RMB795B Basic Documentation

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Note
Overflow value
Set and reset meter
readings
Display values
Notes
Free text
Siemens
Building Technologies
Unit and decimal place depend on unit and format displayed.
This value can only be changed via software tool OCI700.1.
Operating line
Overflow value

15.2.5 Setting and resetting meter readings

In case of deviations, service staff can adjust the pulse meter reading via operating
line "Meter reading current". This value can only be changed via software tool
OCI700.1.
Using datapoint "Reset monthly values", the last 15 monthly values can be deleted.
The current meter reading is retained.
Main menu > Commissioning > Settings ... or
Main menu > Settings > Data acquisition > Meter > Meter 1...4 >
Operating line
Reset monthly values

15.2.6 Display meter readings

The current meter reading, the date and the reading of the last 15 months are
displayed.
Main menu > Data acquisition > Meter 1...4 >
Operating line
Meter reading current
Unit
[Readout 1] date
[Readout 1] meter reading
...
[Readout 15] date
[Readout 15] meter reading
• The following operating lines apply analogously to meters 2 through 4.
• The monthly values are stored at midnight at the end of the month.
• The 15 monthly values can be deleted at the password level via operating line
"Reset monthly values".

15.2.7 Assign texts

A specific text can be assigned to each meter. This text appears as menu text and
operating line text on the operating pages.
Main menu > Commissioning > Settings ... or
Main menu > Settings > Data acquisition > Meter > Meter 1...4 >
Operating line
Meter 1...4
Refer to section 6.5.4 for an overview of all editable texts and on how to reset
them.
Central control unit RMB795B
Data acquisition
Range
0...999'999'999
Range
No, yes
Comments
0...999'999'999
As per configured display format.
Range
Max. 20 characters.
Factory setting
99'999'999 kWh
Factory setting
No
Factory setting
Meter 1...4
125 / 144
CE1P3122en
18.01.2012