Configuration
Setting values
Function diagrams
Key
Switch to desired room
operating mode
60 / 144
Siemens
Building Technologies
Main menu > Commissioning > Extra configuration > Room group 1...10 > Room operating
mode >
Operating line
Timer function
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Room group 1....10 > Room operating mode >
Operating line
Timer function
The function diagrams below show the impact of the timer function on the effective
room operating mode with 2 different setting values.
a) Setting value 60 min:
A
60 min
ON
B
OFF
C
a) Setting value 720 min:
A
720 min
B
ON
OFF
C
A
Time switch (
)
B
Switching command via digital input for "Timer function" with time set for Comfort mode.
C
Effective room operating mode
The digital input enables the plant to be constantly switched to the desired room
operating mode. The required operating mode can be selected via data point
"Room operating mode input 1" on menu Room group X > Room operating
mode >.
This operating mode is active until the signal at the control input is no longer
present. Only then does the normal 7-day program resume operation.
Central control unit RMB795B
Function block: "Room group"
Adjustable values / remarks
---, N.X1, N.X2, ... (digital inputs only).
Range
0...720 min
60 min
60 min
Factory setting
60 min
CE1P3122en
18.01.2012