Multiple Use Of Sensors; Digital Inputs (Xx); Use And Activation; Normally Closed - Siemens RMB795B Basic Documentation

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Problem and solution
Configuration
Setting values
Use
Activation
Setting values
Setting values
Siemens
Building Technologies
7.2.6

Multiple use of sensors

Not all sensor signals can be routed via bus to another device.
For this reason, function "Multiple use of sensors" allows for wiring a passive signal
at an input terminal directly to a Y-output and provide it as a DC 0...10 V signal.
The signal can then be fed to other devices.
Main menu > Commissioning > Extra configuration > Sensor multiple use
Operating line
Signal Y N.X1...
Conversion of a Ni 1000 or Pt 1000 signal to a DC 0...10 V signal is made via
parameter setting "Value low" or "Value high".
See Sec. 7.5.2 "Outside temperature at terminal".
7.3

Digital inputs (Xx)

7.3.1

Use and activation

Control function signals can be connected to the digital inputs.
The inputs can be activated as described under Sec. 7.1.2 "Activate function".
7.3.2

Normally closed

Normally closed can be defaulted for each digital input:
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line
Normally closed
7.3.3

Texts for logical states 0 and 1

Each digital input can be assigned the logic states 0 and 1 and one free text (e.g.
on/off, full/empty, etc.). A default text is displayed on the impacted input.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Inputs > ...X...
Operating line
Text for: Logic 0
Text for: Logic 1
Central control unit RMB795B
Inputs
Adjustable values / remarks
Activate function by assigning an input terminal to the
output terminal.
Range
Open, closed.
Range
Max. 20 characters.
Max. 20 characters.
Factory setting
Open.
Factory setting
0
1
49 / 144
CE1P3122en
18.01.2012

Hide quick links: