Troubleshooting; Functional Check / Wiring Test; Analog Inputs (Xx); Activation And Type - Siemens RMB795B Basic Documentation

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Fault status messages
Note
First set input
identifiers
Exercise caution when
changing identifiers!
Checking the
measured values
Activation
Siemens
Building Technologies
No.
Text
100
Simulation inputs active
The fault message remains active until "Simulation" is returned to "----". This is to
make certain it will not be forgotten on the plant to reset the simulation.
The simulated input terminal value is used only locally; it is not sent via bus to
other controllers.
7.1.5

Troubleshooting

With some of the function blocks, defined inputs are mandatory, such as the
outside temperature. For this reason, when making a configuration, the input
identifiers must always be set first.
If input identifiers are changed after configuration of other function blocks, certain
functions for the other blocks may be set to inactive, as they would have to work
with units invalid for the particular block.
7.1.6

Functional check / wiring test

During the wiring test, the measured values of all inputs can be checked as follows:
Main menu > Commissioning > Wiring test > Inputs >
Operating line
N.X1
...
RMZ787(2).X4
7.2

Analog inputs (Xx)

7.2.1

Activation and type

The analog inputs can be activated as described in Sec. 7.1.2 "Activate function".
With the analog inputs, the following settings can be made:
• Type
• Measuring range
• Measured value correction
Central control unit RMB795B
Inputs
Effect
Non urgent message; must not be
acknowledged.
Adjustable values / remarks
Display of the current measured value.
Ditto
Ditto
45 / 144
CE1P3122en
18.01.2012