Siemens RMB795B Basic Documentation page 68

Central control unit for room controllers rxb/rxl and room thermostats rdg/rdf/rdu
Hide thumbs Also See for RMB795B:
Table of Contents

Advertisement

Configure operating
mode relays 1 and 2
Settings
Meaning of adjustable
values
Note on factory setting
Connect room
operating modes
68 / 144
Siemens
Building Technologies
Main menu > Commissioning > Extra configuration > Room group 1...10 > Room operating
mode
Operating line
Operating mode relay
1
Operating mode relay
2
On the Settings menu, the operating mode relay to be energized can be defined
for each room operating mode. This ensures full flexibility, offering a host of
applications.
Main menu > Settings > Room group 1...10 > Room operating mode
Operating line
Comfort relay
control
Precomfort relay
control
Economy relay
control
Protection relay
control
The adjustable values previously listed under "Settings" mean the following for the
operating mode relay:
Value set
State of relay R1
---
Normally closed
R1
Operating
position
R2
Normally closed
R1 + R2
Operating
position
The factory setting was chosen to allow for direct connection of the digital outputs
to the digital inputs of the Synco™200 controller.
As the Synco™ 200 controllers do not know operating mode Precomfort, the
central control unit RMB795B switches the Synco™ 200 controllers directly to
Comfort in the event of Precomfort. This setting can be changed to suit individual
needs.
When the digital outputs "Relays 1 /2" of a "Room group" function block are
connected to the room operating inputs of 1 or several other "Room group" function
blocks, the following assignments for the "Relays 1 /2" outputs are to be made:
Operating line
Assignment
Comfort.
R2
Precomfort
R1
Economy.
R1 + R2
Protection.
---
Central control unit RMB795B
Function block: "Room group"
Adjustable values / remarks
---, N.Q1 ... (only free relays) /
assignment of operating mode relays
---, N.Q1 ... (only free relays) /
assignment of operating mode relays
Adjustable values / remarks
--, R1, R2, R1 + R2
--, R1, R2, R1 + R2
--, R1, R2, R1 + R2
---, R1, R2, R1 + R2
State of relay R2
Normally closed
Normally closed
Operating
position
Operating
position
Factory setting
---
---
R2
R1 + R2
CE1P3122en
18.01.2012