11.3 General Faults
This table describes situations where the soft starter does not operate as expected but does not trip or give a
warning.
Symptom
The soft starter does not respond
to the START or RESET button on
the controller.
The soft starter does not respond
to commands from the control
inputs.
Possible cause/Suggested solution
This is a name selected for a programmable input. Refer to Input A trip.
This trip is not adjustable.
The starter is not receiving mains supply on one or more phases.
Check that the main contactor closes when a start command is given, and remains closed
until the end of a soft stop. Check the fuses. If testing the soft starter with a small motor, it
must draw at least 10% of the starter's programmed FLC setting on each phase.
Related parameters: None
This is a name selected for a programmable input. Refer to Input A trip.
There is a problem with the connection between the soft starter and the optional expansion
card. Remove and reinstall the card. If the problem persists, contact your local distributor.
Related parameters: None
This is a name selected for a programmable input. Refer to Input A trip.
The motor has experienced a sharp drop in current, caused by loss of load. Causes can
include broken components (shafts, belts or couplings), or a pump running dry.
Related parameters: 5C, 5D, 6D
Mains voltage has fallen below the level selected. Causes can include an undersized supply
or adding a large load to the system.
Related parameters: 5G, 5H, 6F
This is a name selected for a programmable input. Refer to Input A trip.
Where 'X' is 1, 2 or 3.
Internal fault (PCB fault). Contact your local supplier for advice.
Related parameters: None
Probable Cause
•
The soft starter may be in Remote control mode. When the soft starter is in
Remote control mode, the Local LED on the starter is off. Press the LCL/RMT
button once to change to Local control.
The soft starter may be in Local control mode. When the soft starter is in
•
Local control mode, the Local LED on the starter is on. Press the LCL/RMT
button once to change to Remote control.
•
The control wiring may be incorrect. Check that the remote start, stop and
reset inputs are configured correctly (refer to
details).
•
The signals to the remote inputs may be incorrect. Test the signalling by
activating each input signal in turn. The appropriate remote control input LED
should activate on the controller.
•
If no external reset is connected, use parameter 6M to set the reset input to
normally open or fit a link across terminals C41, C42 on the controller.