CONTROLLER
6.12 Input/Output Status
Temperature Sensors State
This screen shows the state of the motor thermistors and RTD/PT100s.
NOTE
The use of RTDs is not supported by this product and this screen will always indicate 0 (ie Open) for RTDs
A->G.
Digital I/O State
This screen shows the current status of the digital inputs and outputs.
The top line of the screen shows the start, stop, reset and programmable inputs A and B, then '00'. The screen shows
input C23~C24 closed with all other inputs open.
The bottom line of the screen shows programmable output A, the fixed Run output, programmable outputs B and C,
then '000'. The screen shows all outputs open.
Analog I/O State
This screen shows the current status of the Analog I/O
NOTE
Input is not supported by this product and this screen will always indicate Input: - - - - %
6.13 Reset Thermal Models
The soft starter's thermal modelling software constantly monitors the motor's performance. This allows the starter
to calculate the motor's temperature and ability to start successfully at any time.
The thermal model for the active motor can be reset if required.
1.
Open the Commissioning Menu.
2.
Scroll to Reset Thermal Models and press
3.
At the confirmation prompt press STORE to confirm or
action. You may have to enter your access code.
4.
Select Reset and press
Selecting Do Not Reset returns to previous screen.
When the thermal model has been reset, the screen will display a confirmation
message then return to the previous screen.
CAUTION
Resetting the motor thermal model will compromise thermal model protection and may compromise
motor life. Only reset the thermal model in an emergency.
26
| MVE User Manual (710-17074-00H)
.
.
Thermistor: 0
RTDs A-->G:OOOOOOO
S = Shrt H=Hot C=Cld O=Opn
Inputs:
Outputs: 0000000
Input: - - - - %
Output A: 04.0mA
Reset Thermal Models
to cancel the
Reset Thermal Models
Temp Sensors State
Digital I/O State
1000000
Analog I/O State
M1 X%
M2 X%
Store to Reset
Do Not Reset
Reset
Need help?