OPERATION
For a timed voltage ramp start, the following are typical values and can be adjusted to suit your specific application:
Add the FLC value of all the connected motors. Use this combined value to set parameter 1A
Load Current
Set parameter 2C
as required (parameter 2B
2
1
7.4

Stop Methods

Coast to Stop
Coast to stop lets the motor slow at its natural rate, with no control from the soft starter. The time required to stop
will depend on the type of load.
Timed Voltage Ramp Soft Stop
Timed voltage ramp stopping reduces the voltage to the motor gradually over a defined time. This can extend the
stopping time of the motor and may avoid transients on generator set supplies.
NOTE
The load may continue to run after the stop ramp is complete.
30
| MVE User Manual (710-17074-00H)
. (Note that the combined value must not exceed the starter rating.)
Initial Current
to 100%, parameter 2D
Start Ramp Time
3
Time
1
Time
Current Limit
).
Initial Current
1:
4
Current Limit
2:
Start Ramp Time
3:
5
4: Full voltage
5: Motor 1 current
6
6: Motor 2 current
Stop Time
1:
to 600%, and set the ramp time
(parameter 2C)
(parameter 2D)
(parameter 2B)
(parameter 2I)
Motor Full