PROGRAMMABLE PARAMETERS
7C – Relay A Off Delay
Range:
0:00 - 5:00 (minutes:seconds)
Description:
Sets the delay for re-opening Relay A.
7D~7I – Output Relays B and C
Parameters 7D~7I configure the operation of Relays B and C in the same way as parameters 7A~7C configure Relay A.
Refer to Relay A for details.
Relay B is a changeover relay.
7D
Relay B Function
•
Relay B On Delay
•
7E
Relay B Off Delay
•
7F
Relay C is a changeover relay.
Relay C Function
7G
•
Relay C On Delay
7H
•
Relay C Off Delay
•
7I
7J – Reserved
Reserved for future use.
7K – Reserved
Reserved for future use.
7L – Reserved
Reserved for future use.
7M – Low Current Flag
The MVE has low and high current flags to give early warning of abnormal operation. The current flags can be
configured to indicate an abnormal current level during operation, between the normal operating level and the
undercurrent or instantaneous overcurrent trip levels. The flags can signal the situation to external equipment via
one of the programmable outputs.
The flags clear when the current returns within the normal operating range by 10% of the programmed flag value.
Range:
1% - 100% FLC
Description:
Sets the level at which the low current flag operates, as a percentage of motor full load current.
7N – High Current Flag
Range:
50% - 600% FLC
Description:
Sets the level at which the high current flag operates, as a percentage of motor full load current.
7O – Motor Temperature Flag
The MVE has a motor temperature flag to give early warning of abnormal operation. The flag can indicate that the
motor is operating above its normal operating temperature but lower than the overload limit. The flag can signal the
situation to external equipment via one of the programmable outputs.
Range:
0% - 160%
Description:
Sets the level at which the motor temperature flag operates, as a percentage of the motor's
thermal capacity.
50
| MVE User Manual (710-17074-00H)
Default:
Default: Run
Default: 0 second
Default: 0 second
Default: Trip
Default: 0 second
Default: 0 second
Default:
Default:
Default:
0 second
50%
100%
80%