PROGRAMMABLE PARAMETERS
10 Start/Stop-2
10A – Start Mode-2
Options:
Constant Current (default)
Description:
Selects the soft start mode.
10B – Start Ramp-2
Range:
0:01 - 3.00 (minutes:seconds)
Description:
Sets the ramp time for current ramp starting (from the initial current to the current limit).
10C – Initial Current-2
Range:
50% - 600%
Description:
Sets the initial start current level for current ramp starting, as a percentage of motor full load
current. Set so that the motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
10D – Current Limit-2
Range:
50% - 600% FLC
Description:
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor
full load current.
10E – Reserved
Reserved for future use.
10F – Kickstart Time-2
Range:
0 - 2000 (milliseconds)
Description:
Sets the kickstart duration. A setting of 0 disables kickstart.
10G – Kickstart Level-2
Range:
100% - 700% FLC
Description:
Sets the level of the kickstart current.
10H – Stop Mode-2
Options:
Coast To Stop (default)
TVR Soft Stop
Description:
Selects the stop mode.
10I – Stop Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Description:
Sets the stop time.
11 RTD/PT100 (Reserved)
This parameter group is reserved for future use.
12 Slip-Ring Motors
These parameters allow the soft starter to be configured for use with a slip-ring motor.
12A – Motor 1 Ramp
Options:
Single Ramp (default)
Dual Ramp
Description:
Selects whether to use a single or dual current ramp profile for soft starting. Set to single ramp for
non-slip ring induction motors, or dual ramp for slip-ring induction motors.
54
| MVE User Manual (710-17074-00H)
Default:
1 second
Default:
400%
Default:
400%
Default:
0000 milliseconds
Default:
500%
Default:
0 second