PROGRAMMABLE PARAMETERS
6C – Input A Trip
Options:
Always Active (default)
Operating Only
Run Only
Description:
Selects when an input trip can occur.
6D – Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Description:
Sets a delay between the input activating and the soft starter tripping.
6E – Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Description:
Sets a delay before an input trip can occur, after the soft starter has entered the state selected in
6C.
6F, 6G, 6H, 6I, 6J – Input B Trip
Parameters 6F~6J configure the operation of Input B, in the same way as parameters 6A~6E configure Input A. Refer
to Input A for details.
Input B Function
6F
Input B Name
6G
Input B Trip
6H
Input B Trip Delay
6I
Input B Initial Delay
6J
6K – Reserved
Reserved for future use.
6L – Reserved
Reserved for future use.
6M – Remote Reset Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the MVE's remote reset input (terminals C41, C42) is normally open or normally
closed.
6N – Reserved
Reserved for future use.
6O – Reserved
Reserved for future use.
6P – Reserved
Reserved for future use.
6Q – Local/Remote
Options:
LCL/RMT Anytime (default)
LCL/RMT When Off
Local Control Only
Remote Control Only
Description:
Selects when the LCL/RMT button can be used to switch between local and remote control, and
enables or disables the local control buttons and remote control inputs.
The STOP button on the controller is always enabled.
The reset input and RESET button on the controller are always enabled.
WARNING
The STOP button on the controller is always enabled. When using two-wire remote control, the soft starter
will restart if the remote start/stop and reset inputs are still active.
48
| MVE User Manual (710-17074-00H)
A trip can occur at any time when the soft starter is receiving power.
A trip can occur while the soft starter is running, stopping or
starting.
A trip can only occur while the soft starter is running.
Default:
Default:
(Default:
(Default:
(Default:
(Default:
(Default:
LCL/RMT button is always enabled.
LCL/RMT button is enabled when the starter is off.
The LCL/RMT button and remote start/stop inputs are disabled.
The START and LCL/RMT) buttons are disabled.
0 second
0 second
Input Trip (N/O))
Input Trip)
Always Active)
0:00)
0:00)