8J – Graph Timebase
Options:
10 seconds
30 seconds
1 minute (default)
5 minutes
Description:
Sets the graph time scale. The graph will progressively replace the old data with new data.
8K – Graph Maximum Adjustment
Range:
0% – 600%
Description:
Adjusts the upper limit of the performance graph.
8L – Graph Minimum Adjustment
Range:
0% – 600%
Description:
Adjusts the lower limit of the performance graph.
8M – Mains Reference Voltage
Range:
100 – 14000 V
Description:
Provides the reference voltage for the analog output and performance graphs.
9 Motor Data-2
The MVE can support two different starting and stopping motor data sets.
To select the secondary motor data set, a programmable input must be configured to parameter set selection
(parameters 6A and 6F) and the input must be active when the soft starter receives a start signal.
NOTE
You can only choose which motor data set to use while the soft starter is stopped.
9A – Reserved
Reserved for future use.
9B – Motor FLC-2
Range:
5 - 1000 A
Description:
Sets the secondary motor's full load current.
9C – Reserved
Reserved for future use.
9D – Reserved
Reserved for future use.
9E – Reserved
Reserved for future use.
PROGRAMMABLE PARAMETERS
10 minutes
30 minutes
1 hour
Default:
400%
Default:
0%
Default:
400 V
Default:
100 A