Control program
t
5s
Putting the circuit to be tested under atmospheric pressure
4
t
7.5s
Time elapsed between the start and the energizing of the main relay "ar"
6
t
22.5s
1st test phase with atmospheric pressure
1
t
5s
Putting the test circuit gas under pressure
3
t
27.5s
2nd test phase with gas pressure
2
t
67.5s
Total duration of seal test, up to burner operation consensus
5
t
22.5s
Return to the programmer stand-by position = preset for a new check.
20
Program execution
AL remote alarm signal
AR main relay with the 'ar...' contacts
AS device fuse
BR shut-down relay with 'br...' contacts
DW external pressure switch (leak test)
EK reset key
GP external pressure switch (of system gas pressure)
HR reset relay with 'hr...' contacts
L1 device fault warning light
SK line switch
I... XI
34 / 44
0006080118_201311
programmer cam contact
Activated terminals of