Diagram Of a DismanTLeD ( C.B. ) CHarLes BergOnZO nOZZLe (WiTHOUT Pin)
Nozzle rating data:
Flow rate kg/h
Spray angle (30° - 45° - 60° - 80°)
Output ratio (1/3 = B3 - 1/5 = B5)
Fuel outlet hole
For the nozzle to operate properly, its "return" section must never be completely closed. This condition must be implemented
properly when igniting the burner for the first time. In practice when the nozzle is operating at the maximum desired output, the
difference between "delivery" to nozzle (pump pressure) and "return" from nozzle (pressure at the return pressure regulator)
pressure must be at least 2 ÷ 3 bar.
Example
PUmP COnneCTiOn Diagram HP
mODeL VBH 1000 ÷ 6000
Fuel outlet
Pump pressure 20 bar
Return pressure 20 - 2 = 18 bar
Return pressure 20 - 3 = 17 bar
15 / 44
0006080118_201311
Viton seal ring
(oil and temperature resistant)
Fuel inlet
Fuel return
Pump pressure 22 bar
Return pressure 22 - 3 = 19 bar
Return pressure 22 - 2 = 20 bar
1
Intake
2
Vacuum gauge connection ¼"
3
Return
4
Pump data plate
5
Delivery to nozzle
6
Pressure gauge connection ¼"
7
Heating element seat
8
Pump pressure regulation screw
Fuel return