1. Installation
1−30
Screw terminaladapter (IP20)
With this adapter the bus can be connected to a 2x5−pin ter
minal strip. Use the second row of connections for the con
tinuing field bus.
The maximum permitted current at the terminals is 4 A. Use
cables with a cross sectional area of min. 0.34 mm
Order this connection from Festo (type: FBA−1−SL−5pol) to
gether with the terminal strip type FBSD−KL−2x5pol.
Screw terminal
adapter
1 2
3 4
5
Fig. 1/8: Pin assignment of the field bus interface (screw
terminal adapter 5−pin)
If you connect the field bus via the terminal strip type
FBSD−KL−2x5pol from Festo, you can implement a T−adapter
function.
Pin no.
1. 0 V bus
2. CAN_L
3. Screening/shield
4. CAN_H
5. 24 V DC bus (max. 4 A)
2x5−pin terminal strip
Festo P.BE−CPX−FB14−E N en 0308a