3. Diagnosis
Byte 0
Byte 1
Error code
Bit
Meaning
0
Generic Error
1
Current
Voltage
3
4
Communication Error
5 ... 6
7
Manufacturer specific
bold = Bit is used by CPX terminal
Tab. 3/7:
Error register (Index 1001 with bit assignment as per DS 301/401)
3−18
Byte 2
Byte 3
Error
Status
Register
bits
Index
Index 1002 (Manufacturer Status Register)
1001
Explanation
Bit is set for each fault
Short circuit/overload in sensor supply (SCS)
Short circuit/overload at outputs (SCO)
V
(undervoltage at outputs)
out
V
(undervoltage at valves)
val
Failure of load voltage at CPX output module or input
module
Node guard, Heart beat, CAN fault
Wire fracture
Other faults
Further diagnostic information is provided by the CPX ter
minal in bytes 3 ... 6 of the Emergency Object (Manufacturer
status register, Index 1002).
Byte 4
Byte 5
CPX
CPX
module no.
fault no.
Byte 6
Byte 7
Additional
reserved
information
on the fault
Festo P.BE−CPX−FB14−E N en 0308a