IBM Power System Series Problem Analysis, System Parts, And Locations page 41

Hide thumbs Also See for Power System Series:
Table of Contents

Advertisement

Table 10. Sensor information, event description, and service action for the 5104-22C, 9006-12P,
9006-22C, or 9006-22P (continued)
Sensor name (Sensor ID)
System Event (0x04)
Boot Progress (0x05)
• PCIE CPU1 Pwr (0x06)
• PCIE CPU2 Pwr (0x07)
• OCC Active 1 (0x08)
• OCC Active 2 (0x09)
Event description
Undetermined system hardware
failure
• System Reconfigured
• OEM System boot event
• Entry added to auxiliary log
• PEF Action
• Timestamp Clock Sync
• Unknown Error
• Unknown Hang
• Unknown Progress
• Lower Non-critical – going low
• Lower Non-critical – going high
• Lower Critical – going low
• Lower Critical – going high
• Lower Non-recoverable – going
low
• Lower Non-recoverable – going
high
• Upper Non-critical – going low
• Upper Non-critical – going high
• Upper Critical - going low
• Upper Critical - going high
• Upper Non-recoverable – going
low
• Upper Non-recoverable – going
high
Device Disabled
• State Deasserted
• Device Enabled
Beginning troubleshooting and problem analysis 27
Service action
Go to "Collecting diagnostic
data" on page 60. Then, go to
"Contacting IBM service and
support" on page 61.
No service action is required.
No service action required.
If the sensor name is OCC Active
1, replace CPU 1. If the sensor
name is OCC Active 2, replace
CPU 2. Go to "5104-22C or
9006-22C locations" on page
63, "9006-12P locations" on
page 75, or "9006-22P
locations" on page 91 to
identify the physical location and
removal and replacement
procedure.
No service action is required.