8 Specification

8.1 Input

Model
Input
Sampling cycle
Temperature
Measurable
range
Humidity
Temperature
Accuracy
Humidity
Contact Input(D.I)
8.2 Output
Model
Control Output
Current
Output(S.C.R)
Temperature
Retransmission
Humidity
Output
Resolution
Renewal Time
Digital
Output
(D.O)
Transistor
R.T.D
R.T.D(Resistance Temperature Detector) : Pt100Ω IEC 751
0 - 5 V d.c ※ In case of using Digital Temperature Sensor (Example:EE99),
VDC
please connect resistance 250 Ω in parallel on the exterior
-100.0 ~ 200.0 ℃
± 0.1 % of F.S
8 points(1a 8 points, 2 COM)
ON : 24 V d.c OFF : Less than 0.1 V d.c Pulse voltage(More than
S.S.R
4 - 20 ㎃ d.c (1 - 5 V) ( Load
resistance : Less than 600 Ω)
4 - 20 ㎃ d.c ( Load resistance : Less than 600 Ω) PV/MV/SV(
Around 8,000 (4 ㎃ - 20 ㎃)
12 points(1c 4 points, 1a 8 points)
Relay
8 points (2 COM)
TH500
500 ㎳
0.0 ~ 100.0 % R.H.
± 2 % of F.S
TH500
load resistance 800 Ω
Cycle time : 1 ~ 1,000 sec
Internal selection)
Around 7,000 (4 ㎃ - 20 ㎃)
500 ms
8 points (1a 8 points)
N.O : 30 V d.c 5 A, 250 V a.c : 5 A
N.C : 30 V d.c 1 A, 250 V a.c : 2 A
24 V d.c 300 ㎃ max (Open Collector)
91
TH300
-100.0 ~ 500.0 ℃
± 0.2 % of F.S
4 points(1a 4 points, 1 COM)
TH300
S.C.R is not available
4 points(1 COM)