Name
Enter a pattern number to be set or select it by
PTN NO.
pressing the
Temp. WAIT
S
Set the deviation range about the temperature set
a
value which will be applied to the standby operation.
RANGE
a
Set the deviation range about the humidity set value
Humi. WAIT
RANGE
which will be applied to the standby operation.
Until it satisfies the deviation range about the set
value which will be applied to the standby operation,
it sets the time that delays the process of segment.
When both of temperature and humidity standby
WAIT TIME
range are being set, both of them must fall within
standby operation range in order to cancel the
standby operation.
SEG progress without
applying standby mode
SEG progress with
applying standby mode
[FIG 57] generally display the standby operation. If process value (PV) does not fall within the
standby range at the changing point from SEG1 to SEG2, it will wait until process value (PV)
falls within the standby range (wait for the set standby time). Here, if standby time elapses, it
will process to the SEG 2 even if the process value (PV) did not fall within the standby range
[FIG 58].
S
Function
w
/
button.
Waiting time
Start Waiting
Operation
Standby operation starts
to on because PV did not fall
within the standby range
[Fig 57] Common waiting operation
50
S
b
t
s
d
b
Waiting Range
Standby operation
becomes cancelled because PV
falls within the standby range
Range
1~100 Pattern
(0 ~ ±300) ℃(TH500)
(0 ~ ±600) ℃(TH300)
(0 ~ ±100) %
0 ~ 99 hour