Hanyoung TH500 Manual page 88

Programmable temperature and humidity controller
Table of Contents

Advertisement

[FIG.138] Program setup menu
Explanation of Program Pattern Setting Screen
Operating Seg.
Under the Temp 25 ℃, Humidity 80% set up temp.
SEG.No.001
& humidity segment for one minute.
Under the Temp 25 ℃, Humidity 80% set up temp.
SEG.No.002
& humidity maintenance segment for one minute.
Under the Temp 50 ℃, Humidity 60%, temp. rise &
SEG.No.003
humidity fall for one minute.
Under the Temp 50 ℃, Humidity 60%, temp. rise &
SEG.No.004
humidity fall for one minute.
Under the Temp 75 ℃, Humidity 40% set up temp
SEG.No.005
rise & humidity fall segment for one minute.
Under the Temp 75 ℃, Humidity 40% set up temp.
SEG.No.006
& humidity maintenance segment for one minute.
Explanation of Program Pattern Setting Screen.
Setting item
Input pattern no. directly or select it by using
PTN NO.
SEG. Page
Press Segment Page Shifting button(
and it moves to 4 segment per each shifting
MENU
Press setting screen and set up setting value of
TEMP.SV
temperature of the segment.
Humi.SV
Press setting screen and set up setting value of humidity of the segment.
Set up operation time of the segment
Hour/Min
Select function of Standby Operation which was set up
Wait
in the Standby Operation Setting Screen.
T.S
Select Time Signal which works at the segment
Among 4 Alarms which was set up in the Patter Alarm Setting Screen,
Alarm
select operation respectively. Pattern Alarm Selection Screen [Fig. 48]
[FIG.139] Program pattern setting
Contents of setting
Explanation
89
Consider
connected
pattern as ne
and repeat it
infinitely
button
1 ~ 100 Pattern
)
TH500 (-100 ~ 200) ℃
TH300 (-100 ~ 500) ℃
(0 ~ 100) %
0 ~ 255hours and 59minutes
1~4 respectively
ON/OFF
Remark
Range
ON/OFF