6.6 D.I Configuration Setting
D.I(Digital Input) is consisted of 3 screens .TH500 has 8 points of D.I and TH300 has 4 point of
D.I (Active Low)
6.6.1 D.I Setting 1
You can assign three operation functions (RUN/STOP, STEP, HOLD) which is related to basic
operation function in the D.I Setting 1[Fig. 109]. User can set up HIGH/LOW operation to these
three operation functions. As LEVEL input, RUN/STOP and HOLD input should maintain their
level continuously. Because STEP operation is EDGE input, it operates one time according to its
setting in case of H->L or L->H. You should enter H and L continuously in order to keep on
STEP operation.
•Overlapping assignment of D.I number is not available in the inputs of RUN/STOP,
STEP, HOLD operation function. Also when input of STEP and HOLD come is at the
same time, it ignores STEP input and it handles HOLD input only.
•Regardless of control action(Running or Stop), external D.I is always displayed and
handled internally according to its input status.
Name
RUN / STOP
Start or end the assigned D/I input signal according to the operation mode (H/L) set.
(LEVEL Input)
In case of running in program control mode, perform the STEP operation (go
STEP
to the next SEG. by force) for the assigned D/I input signal according to the
(EDGE Input)
operation mode (H/L) set.
In case of running in program control mode, perform the HOLD operation
HOLD
(hold the current SEG. operation unlimitedly regardless of set time) for the
(LEVEL Input)
assigned D/I input signal according to the operation mode (H/L) set.
[FIG. 109] D/I setting 1
Function
74