6.3 Retransmission output setting

Temperature & Humidity retransmission output can be selected on Control Output Setting screen 3
[Fig. 87] & Control Output Setting screen 4 [Fig. 88].
[Fig. 87] Temperature retransmission
output setting screen
※ The contents of Control Output Setting screen 3 & Control Output Setting
screen 4 are same.
Setting item
Select type of RET (Retransmission output) against temperature. It is used as input in
T.Source
the recorder etc. output signal is 4 - 20 ㎃ d.c and select one among PV (Process
Value), MV (Manipulated Value), SV (Setting Value).
Scale value against temperature output range will be selected 4 - 20 ㎃
d.c But if MV selected, output will be the percentage of setting value
T.Range
against 4 - 20 ㎃ d.c It means if you select 50 %, output will be 12 ㎃ d.c
Input Current Bias Value in order to delete deviation. When pressing
Temperature retransmission output bias screen[Fig. 89] will be shown up. If output value is
different compared to the standard output 50.0, please touch
Out. Adjust
standard output as 50.0. In this case, output signal which is corresponded to 50.0 will be
generated. Please measure this value after inputting this value on the measured output
setting screen, please remove
S.Burnout
between 0.0 ㎃ d.c and 4.0 ㎃ d.c
Output
[Fig. 88] Humidity retransmission
output setting screen.
Explanation
button.