7.2 Setting Output
7.2.1 Control Output Setting
TH500
TH500
T.Out type
TH300
You can set up when you select S.S.R output. Output cycle means ON/OFF
T.SSR Out
period
operation time in the proportional band.(Initial value : 1 sec)
Select cooling control(direct operation) or heating control
T.Out direct
(Reverse operation). (Initial value : Reverse operation)
Output could be controlled and its range is -5.00% (3.2 ㎃) ~ 105.00%
T.Out range
(20.8 ㎃) (Initial value : 0.00 ~ 100.00%)
7.2.2 Retransmission Output Seting (Control Output Setting 3, Control Output Setting 4)
[Fig.129] Temp.Retransmission Output Setting
[FIG.128] Control output setting 1
S.S.R or S.C.R(4 - 20 ㎃) could be used as a control output
(Initial value : S.S.R)
Control output is S.S.R only.
84
TH300
[Fig.130] Humidity Retransmission Output Setting