Setting item
Select the type of RET(Retransmission output) against temperature. It is used as an
input in the recorder etc. Output signal is 4 - 20 ㎃ d.c and select one among
T.Source
PV(Process Value),MV(Manipulated Value),SV(Setting Value).
Scale value against temp. output range will be selected 4 - 20 ㎃ d.c. But if MV is
T.Range
selected, output will be the percentage of setting value against
4 - 20 ㎃ d.c It means that output will be 12 ㎃ d.c if you select 50 %.
Input Bias value in order to remove deviation value of retransmission output.
Out. Adjust
When touching
In case of sensor loof brake, select between 0.0 ㎃ d.c and 4.0 ㎃ d.c
S.Burnout output
※ Humidity setting method is the same as Temperature setting method.
7.3 Inner Signal Set
[FIG.131] Inner Signal Set
When controlling refrigerator and dehumidifier separately by external switch, it can be used
generally with input-output setting only. But in case it needs to control (On/Off) refrigerator &
dehumidifier under desired temperature and humidity, it' s convenient to use Inner Signal. Please
refer to the below example, select setting and use it.
(Example 1) Control refrigerator & dehumidifier automatically
Inner Signal
Signal Subject
No.
Temperature
I/S No.1
Range : -100 ~ 30 ℃
Subject : Humidity
I/S No.2
Range : 0 ~ 70 %
Explanation
, [Fig.89] & [Fig.90] will be displayed.
Signal Type &
Range
Type : TSV
Direction : Within Range
Type : TSV
Direction : Within Range
85
[FIG.132] D.O Output setup1
Output
Delayed
Allocation(D.O)
Time
Connect refrigerator
1 minute
to 5th Relay
Connect dehumidifier
10 seconds
to 6th Relay