i.8 Parameter Table

No.
Name
Drive Mode Unit
o1-01
Monitor Selection
User Monitor Selection
o1-02
after Power Up
HOA Keypad Operator
o1-03
Display Selection
User Monitor Selection
o1-06
Mode
Second Line Monitor
o1-07
Selection
Third Line Monitor
o1-08
Selection
Frequency Reference
o1-09
Display Units
User-Set Display Units
o1-10
Maximum Value
User-Set Display Units
o1-11
Decimal Display
Frequency Reference
o1-13
and Frequency Related
Monitor Custom Units 1
Frequency Reference
o1-14
and Frequency Related
Monitor Custom Units 2
Frequency Reference
o1-15
and Frequency Related
Monitor Custom Units 3
F1 Key Function
o1-16
Selection
F2 Key Function
o1-17
Selection
78
Description
Selects the content of the last monitor that
is shown when scrolling through Drive
Mode display. Enter the last three digits of
the monitor parameter number to be
displayed: Uo-oo.
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User Monitor
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of
motor poles setting in E2-04, E4-04, or
E5-04)
3: User-selected units (set by o1-10 and
o1-11)
0: 3 Monitor Sequential
(Displays the next two sequential monitors)
1: 3 Monitor Selectable (o1-07 and o1-08
selected monitor are shown)
Selects the monitor that is shown in the
second line.
Selects the monitor that is shown in the
third line.
Sets unit display for the frequency
reference parameters and frequency related
monitors when o1-03 > 40.
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second)
8: Bar (Bar)
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: Custom units (Determined by o1-12)
16: No unit
These settings define the display values
when o1-03 is set to 3.
o1-10 sets the display value that is equal to
the maximum output frequency.
o1-11 sets the position of the decimal
position.
Sets the customer-specified unit display for
the frequency reference parameters and
frequency related monitors when o1-03 = 3
and o1-09 = 15 as custom units.
Sets the customer-specified unit display for
the frequency reference parameters and
frequency related monitors when o1-03 = 3
and o1-09 = 15 as custom units
Sets the customer-specified unit display for
the frequency reference parameters and
frequency related monitors when o1-03 = 3
and o1-09 = 15 as custom units
0: Standard
1: Monitor
2: Drive/Bypass (DRV/BYP)
3: Bypass Run Command (RUN BYP)
4: Toggle Relay Output (RLY)
0: Standard
1: Monitor
2: Drive/Bypass (DRV/BYP)
3: Bypass Run Command (RUN BYP)
4: Toggle Relay Output (RLY)
No.
Name
User Defined Parameter
o1-18
Upper
User Defined Parameter
o1-19
Lower
OFF Key Function
o2-02
Selection
User Parameter Default
o2-03
Value
Drive Model Selection Enter the drive model. Setting required only
o2-04
Frequency Reference
o2-05
Setting Method
Selection
Operation Selection
o2-06
when HOA Keypad is
Disconnected
Motor Direction at
o2-07
Power Up when Using
Operator
Selection of Parameter
o2-19
Write During UV
Copy Function
o3-01
Selection
Copy Allowed
o3-02
Selection
Cumulative Operation
o4-01
Time Setting
Cumulative Operation
o4-02
Time Selection
Cooling Fan Operation
o4-03
Time Setting
Capacitor Maintenance
o4-05
Setting
DC Bus Pre-Charge
o4-07
Relay Maintenance
Setting
o4-11
U2, U3 Initialization
kWh Monitor
o4-12
Initialization
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
Description
Allows the user to set values that can be
used as reference information.
Allows the user to set values that can be
used as reference information.
0: Disabled. OFF key is disabled in
REMOTE operation.
1: Enabled. OFF key is always enabled.
0: No change
1: Set defaults. Saves parameter settings as
default values for a User Initialization.
2: Clear all. Clears the default settings that
have been saved for a User Initialization.
if installing a new control board.
0: ENTER key must be pressed to enter
a frequency reference.
1: ENTER key is not required. The
frequency reference can be adjusted using
the up and down arrow keys only.
0: The drive continues operating if the HOA
keypad is disconnected.
1: An oPr fault is triggered and the motor
coasts to stop.
0: Forward
1: Reverse
This parameter requires assigning drive
operation to the HOA keypad.
Selects whether parameter settings can be
changed during a control circuit
undervoltage condition. Used with built-in
24 V Power Supply Unit models.
0: Forward
1: Reverse
0: No action
1: Read parameters from the drive, saving
them onto the HOA keypad.
2: Copy parameters from the HOA keypad,
writing them to the drive.
3: Verify parameter settings on the drive to
check if they match the data saved on the
HOA keypad.
0: Read operation prohibited
1: Read operation allowed
Sets the value for the cumulative operation
time of the drive in units of 10 h.
0: Logs power-on time
1: Logs operation time when the drive
output is active (output operation time).
Sets the value of the fan operation time
monitor U4-03 in units of 10 h.
Sets the value of the Maintenance Monitor
for the capacitors. See U4-05 to check when
the capacitors may need to be replaced.
Sets the value of the Maintenance Monitor
for the soft charge bypass relay. See U4-06
to check when the bypass relay may need
to be replaced.
0: U2-oo and U3-oo monitor data is
not reset when the drive is initialized
(A1-03).
1: U2-oo and U3-oo monitor data is
reset when the drive is initialized (A1-03).
0: U4-10 and U4-11 monitor data is not
reset when the drive is initialized
(A1-03).
1: U4-10 and U4-11 monitor data is reset
when the drive is initialized (A1-03).