YASKAWA Z1000U Series Quick Start Manual page 76

Low harmonic hvac matrix drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

i.8 Parameter Table
No.
Name
Multi-Function Analog
H4-03
Output Terminal FM
Bias
Multi-Function Analog
H4-04
Output Terminal AM
Monitor Selection
Multi-Function Analog
H4-05
Output Terminal AM
Gain
Multi-Function Analog
H4-06
Output Terminal AM
Bias
Multi-Function Analog
H4-07
Output Terminal FM
Signal Level Selection
Multi-Function Analog
H4-08
Output Terminal AM
Signal Level Selection
H5-01 Drive Node Address
Communication Speed
H5-02
Selection
Communication Parity
H5-03
Selection
Stopping Method After
H5-04
Communication Error
(CE)
H5-05 Communication Fault
Detection Selection
H5-06 Drive Transmit Wait
Time
H5-07 RTS Control Selection
Communication
H5-08
Protocol Selection
H5-09 CE Detection Time
76
Description
Sets the signal level at terminal FM that is
equal to 0% of the selected monitor value.
Selects the data to be output through multi-
function analog output terminal AM.
Set the desired monitor parameter to the
digits available in Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal AM that is
equal to 100% of the selected monitor
value.
Sets the signal level at terminal AM that is
equal to 0% of the selected monitor value.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Selects drive station slave number (address)
for MEMOBUS/Modbus terminals R+, R-,
S+, S-.
Note:
Cycle power for the
setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Note:
Cycle power for the
setting to take effect.
0: No parity
1: Even parity
2: Odd parity
Note:
Cycle power for the
setting to take effect.
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
4: Run at d1-04
0: Disabled
1: Enabled. If communication is lost for
more than two seconds, a CE fault will
occur.
Set the wait time between receiving and
sending data.
Note:
Cycle power for the
setting to take effect.
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when
sending.
Note:
Cycle power for the
setting to take effect.
0: MEMOBUS/Modbus
1: N2 (Metasys)
2: P1 (APOGEE FLN)
3: BACnet
Sets the time required to detect a
communications error.
Adjustment may be needed when
networking several drives.
No.
Name
Unit Selection for
H5-10
MEMOBUS/Modbus
Register 0025H
Communications
H5-11
ENTER Function
Selection
Run Command Method
H5-12
Selection
L1-01 Motor Overload
Protection Selection
L1-02 Motor Overload
Protection Time
Motor Overheat Alarm
L1-03
Operation Selection
(PTC input)
Motor Overheat Fault
L1-04
Operation Selection
(PTC input)
Motor Temperature
L1-05
Input Filter Time (PTC
input)
L1-08 oL1 Current Level
Continuous
L1-13
Electrothermal
Operation Selection
Momentary Power Loss
L2-01
Operation Selection
Momentary Power Loss
L2-02
Ride-Thru Time
Momentary Power Loss
L2-03
Minimum Baseblock
Time
Frequency Reference
L4-05
Loss Detection
Selection
Frequency Reference at
L4-06
Reference Loss
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
Description
0: 0.1 V units
1: 1 V units
0: Drive requires an Enter command
before accepting any changes to
parameter settings.
1: Parameter changes are activated
immediately without the Enter command.
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
0: Disabled
1: General purpose motor (standard fan
cooled)
4: PM motor with variable torque
Default setting is determined by parameter
A1-02, Control Method Selection.
Sets the motor thermal overload protection
(oL1) time.
Sets operation when the motor temperature
analog input
(H3-02 or H3-10 = E) exceeds the alarm
level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the
deceleration time in C1-09)
3: Alarm only ("oH3" will flash)
Sets stopping method when the motor
temperature analog input (H3-02, or H3-10
= E) exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the
deceleration time in C1-09)
Adjusts the filter for the motor temperature
analog input (H3-02, or H3-10 = E).
Sets the reference current for motor thermal
overload detection for the motor in
amperes.
0: Disabled
1: Enabled
2: Enable using Real Time Clock
0: Disabled.
Drive trips on Uv1 fault when power is lost.
1: Recover within the time set in L2-02.
Uv1 will be detected if power loss is longer
than L2-02.
2: Recover as long as CPU has power.
Uv1 is not detected.
Sets the Power Loss Ride-Thru time.
Enabled only when L2-01 = 1.
Sets the minimum wait time for residual
motor voltage decay before the drive output
reenergizes after performing Power Loss
Ride-Thru.
Increasing the time set to L2-03 may help
if overcurrent or overvoltage occur during
Speed Search or during DC Injection
Braking.
Note: Default setting is dependent upon
parameter o2-04, Drive Model Selection.
0: Stop. Drive stops when the frequency
reference is lost.
1: Run. Drive continues operation
according to the setting of L4-06.
Sets the percentage of the frequency
reference that the drive should run with
when the frequency reference is lost.