i.4 Electrical Installation
u
Terminals A1, A2, and A3 Input Signal Selection
Terminals A1, A2, and A3 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as
explained in
Table
i.13. Set parameters H3-01, H3-05, and H3-09 accordingly as shown in
Note:
If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
Setting
V (top position)
I (bottom position)
No.
Parameter Name
H3-01
Terminal A1 signal level selection
H3-05
Terminal A3 signal level selection
H3-09
Terminal A2 signal level selection
u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
as explained in
Table
i.15. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Terminal
Terminal AM
Terminal FM
No.
Parameter Name
H4-07 Terminal FM signal level selection
H4-08 Terminal AM signal level selection
34
Figure i.22 Terminal A2 Set to Current Input; A1 and A3 Set to Voltage Input
Table i.13 Jumper S1 Settings
Table i.14 Voltage/Current Selection Parameter Details
Selects the signal level for terminal A1.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
Selects the signal level for terminal A3.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
Table i.15 Jumper S5 Settings
Voltage Output
V
FM
AM
V
FM
AM
Table i.16 Parameter H4-07 and H4-08 Details
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
Jumper S1
V
I
A1 A2 A3
Description
Voltage input (-10 to +10 V or 0 to 10 V)
Current input (4 to 20 mA or 0 to 20 mA)
Description
I
I
Description
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
Table
i.14.
Setting
Default
Range
Setting
0 to 3
0 to 3
0 to 3
Current Output
V
I
FM
AM
V
I
FM
AM
Setting Range
Default Setting
0 to 2
0
0
0
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000u cimr-zu series

Table of Contents