YASKAWA Z1000U Series Quick Start Manual page 71

Low harmonic hvac matrix drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

Item
Area of Use
Ambient Temperature
Humidity
Environment
Storage Temperature
Altitude
Vibration/Shock
Standards
Protection Design
<1> Current derating is required. Select control modes in accordance with drive capacity.
<2> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors
and with changing motor temperature. Contact Yaskawa for consultation.
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<4> Momentary motor power ride-thru during utility power loss designates the time the drive is able to maintain control over a motor operating at full
load after utility power is lost. Actual specifications may vary depending on motor characteristics.
<5> An auxiliary 24 VDC Control Power Supply option is required if the application needs to maintain control power long after a 2 second momentary
power loss.
<6> Ground protection is triggered when a ground short circuit occurs while the drive is running. The ground protection cannot be provided when the
impedance of the ground fault path is too low, or when the drive is powered up while a ground fault is present at the output.
<7> An IP20/UL Type 1 enclosure drive requires a UL Type 1 kit.
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
Indoors
IP20/UL Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F)
95 RH% or less (no condensation)
-20 °C to +60 °C (-4 °F to +104 °F) (short-term temperature during transportation)
Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
2
10 to 20 Hz: 9.8 m/s
(2o0028 to 2o0248 and 4o0011 to 4o0414)
2
20 to 55 Hz: 5.9 m/s
(2o0028 to 2o0081 and 4o0011 to 4o0077)
2
20 to 55 Hz: 2.0 m/s
(2o0104 to 2o0248 and 4o0096 to 4o0414)
• UL508C
• IEC/EN 61800-3, IEC/EN 61800-5-1:2007
<7>
IP00/Open Type enclosure
Specification
, IP20/UL Type 1 enclosure
i.7 Drive Specifications
71