YASKAWA Z1000U Series Quick Start Manual page 74

Low harmonic hvac matrix drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

i.8 Parameter Table
No.
Name
b5-41
PID Unit Selection
PID Output Monitor
b5-42
Calculation Method
Custom PID Output
b5-43
Monitor Setting 1
Custom PID Output
b5-44
Monitor Setting 2
Custom PID Output
b5-45
Monitor Setting 3
PID Setpoint Monitor
b5-46
Unit Selection
Reverse Operation
b5-47
Selection 2 by PID
Output
Energy Saving Control
b8-01
Selection
C1-01 Acceleration Time 1
C1-02 Deceleration Time 1
C1-03 Acceleration Time 2
C1-04 Deceleration Time 2
C1-11 Accel/Decel Time
Switching Frequency
C2-01 S-Curve Characteristic
at Accel Start
C2-02 S-Curve Characteristic
at Accel End
74
Description
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second)
8: Bar (Bar)
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
0: Linear - the monitor displays PID
output
1: Square root - the monitor displays square
root PID output
2: Quadratic - the monitor displays 1/(PID
output)
3: Cubic - the monitor displays 1/(PID
output)
Set maximum monitor value at maximum
frequency.
U5-07 and U5-08 show Custom PID
output.
U5-43 shows the upper four digits and
U5-44 shows the lower four digits.
It shows 999999.99 maximum.
Sets the minimum display value at zero
speed.
b5-07 and b5-08 show Custom PID output.
This function is effective when b5-42 is set
to 1 (Linear unit)
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second)
8: Bar (Bar)
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
Reverse operation selection when b5-01 =
3
0: Reverse Disabled
1: Reverse Enabled
0: Disabled
1: Enabled
Note: Default setting is dependent upon
parameter A1-02, Control Method
Selection.
Sets the time to accelerate from 0 to
maximum frequency.
Sets the time to decelerate from maximum
frequency to 0.
Sets the time to accelerate from 0 to
maximum frequency.
Sets the time to decelerate from maximum
frequency to 0.
Sets the frequency to switch between accel/
decel time settings
S-curve at acceleration start.
S-curve at acceleration end.
No.
Name
C6-02 Carrier Frequency
Selection
C6-03 Carrier Frequency
Upper Limit
C6-04 Carrier Frequency
Lower Limit
C6-05 Carrier Frequency
Proportional Gain
C7-60 Output Voltage Limit
Mode Selection
d1-01 to
Frequency Reference 1
d1-16
to 4; 16
Jog Frequency
d1-17
Reference
Frequency Reference
d2-01
Upper Limit
Frequency Reference
d2-02
Lower Limit
Master Speed Reference
d2-03
Lower Limit
d3-01
Jump Frequency 1
d3-02
Jump Frequency 2
d3-03
Jump Frequency 3
d3-04
Jump Frequency Width
E1-03 V/f Pattern Selection
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
Description
1: 4.0 kHz
2: 6.0 kHz
3: 8.0 kHz
4: 10.0 kHz
F: User-defined (determined by C6-03
through C6-05)
Note: Default setting is dependent upon
parameters A1-02, Control Method
Selection, and o2-04, Drive Model
Selection.
Determines the upper and lower limits for
the carrier frequency.
Carrier Frequency
C6-03
C6-04
Output Frequency
× (C6-05) × K
Output
Frequency
E1-04
Max Output
Frequency
0: Harmonic suppression priority mode
1: High output voltage mode
Sets the frequency reference for the drive.
Setting units are determined by parameter
o1-03.
Sets the Jog frequency reference. Setting
units are determined by parameter o1-03.
Sets the frequency reference upper limit as
a percentage of the maximum output
frequency.
Sets the frequency reference lower limit as
a percentage of the maximum output
frequency.
Sets the lower limit for frequency
references from analog inputs as a
percentage of the maximum output
frequency.
The drive accelerates and decelerates the
motor through the prohibited frequency
ranges.
Parameters must be set so that d3-01 ≥
d3-02 ≥ d3-03.
Sets the dead-band width around each
selected prohibited frequency reference
point.
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f E1-04 through E1-13
settings define the V/f pattern