i.4 Electrical Installation
Drive
Terminal
Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0361
<1>
p1, n1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4o0414
<1>
p1, n1
<1> Take additional measures in accordance with IEC/EN 61800-5-1:2007 when wiring an EMC filter is installed.
Installation on page 80
u
Main Circuit Terminal and Motor Wiring
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage
to the drive, phase-advancing capacitors, LC/RC noise filters, or ground fault circuit interrupters.
n
Ground Wiring
Follow the precautions below when wiring the ground for one drive or a series of drives.
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize
the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could
result in death or serious injury.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (200 V class: ground to 100 Ω or less; 400 V class: ground
to 10 Ω or less). Improper equipment grounding could result in death or serious injury by contacting ungrounded electrical equipment.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper
equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in
abnormal operation of drive or equipment.
Refer to
Figure i.16
when using multiple drives. Do not loop the ground wire.
28
For USA and Canada
Recomm. Gauge
mm
2
(AWG, kcmil)
(AWG, kcmil)
95 × 2
(4/0 × 2P)
(3/0 to 4/0 × 2P)
95 × 2
(4/0 × 2P)
(3/0 to 4/0 × 2P)
50
(1/0)
2.5
(14)
150 × 2
(300 × 2P)
(4/0 to 300 × 2P)
150 × 2
(300 × 2P)
(4/0 to 300 × 2P )
50
(1/0)
2.5
(14)
for details.
Figure i.16 Multiple Drive Wiring
For South America
Wire Range
Recomm. Gauge
mm
2
mm
2
(AWG, kcmil)
70 to 95 × 2
95 × 2P
(4/0 × 2P)
70 to 95 × 2
95 × 2P
(4/0 × 2P)
50 to 150
95
(1/0 to 300)
(4/0)
2.5 to 4
2.5
(14 to 12)
(14)
95 to 150 × 2
95 × 2P
(4/0 × 2P)
95 to 150 × 2
95 × 2P
(4/0 × 2P)
50 to 240
95
(1/0 to 400)
(4/0)
2.5 to 4
2.5
(14 to 12)
(14)
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
Screw
Wire Range
Size
mm
2
(AWG, kcmil)
70 to 95 × 2P
M10
(3/0 to 4/0 × 2P)
70 to 95 × 2P
M10
(3/0 to 4/0 × 2P)
70 to 150
M12
(3/0 to 300)
2.5 to 4
M4
(14 to 12)
95 to 150 × 2P
M12
(4/0 to 300 × 2P)
95 to 150 × 2P
M12
(4/0 to 300 × 2P )
70 to 240
M12
(3/0 to 400)
2.5 to 4
M4
(14 to 12)
Refer to Internal EMC Filter
Tightening
Torque
N·m (lb.in.)
15 to 20
(130 to 173)
31.4 to 39.2
(278 to 347)
1.2 to 2.0
(10.4 to 17.4)
25 to 35
(217 to 304)
31.4 to 39.2
(278 to 347)
1.2 to 2.0
(10.4 to 17.4)