Set up overheat detection using a PTC using parameters L1-03, L1-04, and L1-05 as explained in the following sections.
u
Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors and permanent magnet motors. The type of Auto-Tuning
used differs further based on the control mode and other operating conditions. Refer to the tables below to select the type of
Auto-Tuning that bests suits the application.
Note:
The drive will only show Auto-Tuning parameters that are valid for the control mode that has been set in A1-02. If the control mode is for
an induction motor, the Auto-Tuning parameters for PM motors will not be available.
n
Auto-Tuning for Induction Motors
This feature automatically sets the V/f pattern and motor parameters E1-oo and E2-oo for an induction motor.
Type
Stationary Auto-Tuning for Line-
to-Line Resistance
Rotational Auto-Tuning for V/f
Control
n
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
No.
T1-01
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotational Auto-Tuning for V/f Control Energy Saving
u
No-Load Operation Test Run
This section explains how to operate the drive with the motor decoupled from the load during a test run.
n
Before Starting the Motor
Check the following items before operation:
• Ensure the area around the motor is safe.
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
Resistance ( )
Tr - 5K (oH3 Alarm Level)
Figure i.56 Motor PTC Characteristics
Table i.31 Types of Auto-Tuning for Induction Motors
Setting
• The drive is used in V/f Control and other Auto-Tuning selections are not
possible.
• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced
T1-01 = 2
with a cable over 50 m long. Assumes Auto-Tuning has already been
performed.
• Should not be used for any vector control modes unless the motor cable has
changed.
• Recommended for applications using Speed Estimation Speed Search or using
the Energy Saving function in V/f Control.
T1-01 = 3
• Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy
for certain functions like torque compensation, slip compensation, Energy
Saving, and Speed Search.
Name
Auto-Tuning Mode Selection
i.5 Start-Up Programming and Operation
Class H
Class F
180 ºC
150 ºC
Tr: threshold value
Temperature
Tr'
Tr
Tr + 5K (oH4 Fault Level)
Application Conditions and Benefits
Setting Range
Default
2, 3 (V/f)
2 (V/f)
Control
Mode
V/f
YES
YES
61