Terminal Configuration
The control circuit terminals should be arranged as shown in
E(G) IG R+ R- S+ S-
A – Terminal Block (TB 2)
B – Terminal Block (TB 5)
C – Terminal Block (TB 1)
n
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
ends.
Terminal
Terminal
Block
IG, R+, R-, S+,
S-, V+, AC, A1,
A2, A3, FM,
AM, AC, RP,
AC, 24V, S1-
TB1, TB2,
S8, SN, SC, SP,
TB3, TB4
M1, M2, M3,
M4, MD, ME,
MF, MA, MB,
MC
E(G)
TB5
E(G)
n
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends
with insulated sleeves. See
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
E
D
M1 M2 M3 M4
MD ME MF
V+ AC A1 A2 A3 FM AM AC
RP AC
24V
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
MA MB MC
C
Figure i.17 Control Circuit Terminal Arrangement
Table
Tightening
Scre
Torque
w
N•m
Size
(lb. in)
mm
0.5 to 0.6
M3
(4.4 to 5.3)
0.5 to 1.0
M3.5
(4.4 to 8.9)
Table i.11
for dimensions.
Figure i.18 Ferrule Dimensions
Figure
i.17.
E(G) IG R+ R- S+ S-
V+ AC A1 A2 A3 FM AM AC
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
D – Terminal Block (TB 3)
E – Terminal Block (TB 4)
i.10. For simpler and more reliable wiring, use crimp ferrules on the wire
Table i.10 Wire Gauges
Bare Wire Terminal
Recomm.
Applicable
wire size
wire size
2
2
(AWG)
mm
(AWG)
Stranded wire:
0.2 to 1.0
0.75 (18)
(24 to 17)
Solid wire:
0.2 to 1.5
(24 to 16)
1.0 (16)
0.5 to 2
1.25 (12)
(20 to 14)
d1
d2
i.4 Electrical Installation
A
M1 M2 M3 M4
MD ME MF
RP AC
24V
MA MB MC
Ferrule-Type Terminal
Recomm.
Applicable
wire size
wire size
2
2
mm
(AWG)
mm
(AWG)
0.25 to 0.5
0.5 (20)
(24 to 20)
B
Wire Type
Shielded wire,
etc.
31