Horizontal Suspension of Drive Models 2o0154 to 2o0248, 4o0156 to 4o0414
To make a wire hanger or frame for use when lifting the drive with a crane, lay the drive in a horizontal position and pass a
wire through the hanging brackets.
NOTICE: Use the hanging brackets on the top and hanging holes of the bottom cover when lifting drive models 2
4
o 0156F, and 4 o 0180F.
2
0154A, 2
4
0156A, 4
n
Vertical Suspension of the Drive
Follow the procedure described below when suspending the drive with eye bolts or hanging brackets.
o 0028 to 2 o 0130 and 4 o 0011 to 4 o 0124
Drive Models 2
WARNING! Crush Hazard. Use an adequate length of wire to ensure a 50° or wider suspension angle as illustrated in
maximum allowable load of the eye bolts cannot be guaranteed when the drive is suspended with the wires at angles less than 50°. Failure
to comply may result in serious injury or death from falling equipment.
1. Pass wire through the holes of the two eye bolts.
2. Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight.
3. Lower the drive when ready to install in the enclosure panel. Stop lowering when near the floor, then slowly begin lowering
the drive again until the drive is placed correctly.
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
0192A, 2
0248,
0180A, and 4
0216 to 4
Figure i.8 Horizontal Suspension of Drive Model 2o0154
Suspending angle:
50° or greater
Figure i.9 Suspension Using Wires and Eye Bolts
2
0154F, 2
0192F, 4
0414
i.3 Mechanical Installation
o 0154F, 2 o 0192F,
0156F, and 4
0180F
Figure
i.9. The
17