i.3 Mechanical Installation
o 0154 to 2 o 0248 and 4 o 0156 to 4 o 0414
Drive Models 2
WARNING! Crush Hazard. Use an adequate length of wire to ensure a 50° or wider suspension angle as illustrated in
maximum allowable load of the eye bolts cannot be guaranteed when the drive is suspended with the wires at angles less than 50°. Failure
to comply may result in serious injury or death from falling equipment.
1. Remove the two hanging brackets from the drive lower side panels and bolt them on the top panel.
Note:
1. Tighten the hanging brackets with the specified tightening torque: M10: 18 to 23 N·m (159 to 204 in-lb),
M12: 32 to 40 N·m (283 to 354 in-lb).
2. Four hanging brackets are attached to the top of IP20/UL Type 1 drives 2o0154F, 2o0192F, 4o0156F, and 4o0180F.
Figure i.10 Location of Hanging Brackets (Drive Models 2o0154 to 2o0248 and 4o0156 to 4o0414)
2. Pass wire through the holes of all four hanging brackets.
3. Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight.
4. Lower the drive when ready to install in the enclosure panel. Stop lowering the drive when it is near the floor, then slowly
begin lowering the drive again until the drive is placed correctly.
u
Drive Dimensions
Refer to the Z1000U HVAC MATRIX Drive User Manual TOEP C710636 10 for IP20/UL Type 1 and IP00/Open Chassis
dimensions.
The Z1000U HVAC MATRIX Drive User Manual is posted on the Yaskawa website, www.yaskawa.com.
18
Suspending angle:
50° or greater
Figure i.11 Drive Suspension Using Wires and Hanging Brackets
(Drive Models 2o0154 to 2o0248 and 4o0156 to 4o0414)
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
NOTICE
Figure
i.10. The