Control Register - Base+6 And Base+7; Table C-6: Control Register - Advantech MIC-3716 Manual

Table of Contents

Advertisement

C.7 Control Register — BASE+6 and BASE+7
The write-only register BASE+6 and BASE+7 allows users to set an
A/D trigger source and an interrupt source.
Write
Bit #
BASE + 7
CAL
BASE + 6
AD16/12
SW
PACER
EXT
Note:
You cannot enable SW, PACER and EXT concurrently.
GATE
IRQEN
86

Table C-6: Control Register

7
6
CNT0
ONE/FH
Software trigger enable bit
1
enable
0
disable.
Pacer trigger enable bit
1
enable
0
disable.
External trigger enable bit
1
enable;
0
disable.
External trigger gate function enable bit.
0
Disable
1
Enable
Interrupt enable bit.
A/D Status Register
5
4
IRQEN
GATE
3
2
1
EXT
PACER
0
SW

Advertisement

Table of Contents
loading

Table of Contents