Replacing basic chassis components
Figure 17: Cooling fan thumbscrew
4. Unseat the cooling fan module by sliding the module horizontally away from the
5. Slide the failed cooling fan module out of the chassis (see C in the diagram).
6. Align the replacement cooling fan module tabs with the four support slots on the
7. Slide the cooling fan module toward the front panel display and into position.
8. Tighten the module thumbscrew and replace the front bezel.
88
Avaya CallPilot® 1002rp Server Maintenance and Diagnostics
display and toward the rack rail (see B in the diagram).
Result: The module power connector unseats from the power connector located
behind the display and LEDs.
chassis.
Ensure that the module is oriented with the thumbscrew, and insert the tabs into the
supporting slots of the chassis.
Result: The fan module connects with slight resistance. The fans rotate and pull air
into the chassis. The cooling fan LED goes out.
December 2010