Sounders Activation By Zone (Control Matrix) - Honeywell NFS Supra Installation And Operating Manual

Conventional fire alarm control panel
Table of Contents

Advertisement

NFS Supra

5.4.4 Sounders activation by zone (Control matrix)

Sounders activation in zones can be configured independently for detectors and call points:
delays operation (Delay 1 and Delay 2) and whether the zone activates or not the sounder.
Sounders activation by zones:
Select sounders configuration menu by pressing SILENCE/RESOUND =ON
Change the selected sounder by pressing RESET:
Led 1 Alarm (Red)
= ON = Sounder 1
Led 2 Disablement (Yellow)
= ON = Sounder 2
For he selected sounder:
Press the ZONE key to select the sounder (Sounder 1 or Sounder 2) activation mode for each
zone (do this operation for all zones and both sounders):
Zone led
Red
Yellow
Activation mode by zone
OFF
ON
Detectors (Eco1000 or 470) with delay / MCP (Zener 5V) without delay
ON
OFF
Detectors (Eco1000 or 470) and MCP (Zener 5V) with delay
ON
ON
Detectors (Eco1000 or 470) and MCP (Zener 5V) without delay
OFF
OFF
Sounder is not activated.
In order to have delayed outputs, Delay 1 or Delay 2 must be configured.
At level 1 or 2, DELAY ON/OFF push-button can be pressed in order to cancel operating
delays
HLS-MN-025 v.04
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
Configuration
Sounder 1 or
Reset
Sounder 2
Option
Configuration)
Zone push-button to
select sounder
activaction
To exit this option, press SILENCE/RESOUND
push-button again.
Installation and Operating Manual
push-button:
Change
(Access
level
3
-
Page 40