Esserbus ® Transponder Iq8Fct Lp, 230 V Ac (Part No. 808621) - Honeywell ESSER FACP Technical Information

Table of Contents

Advertisement

Periphery components for ESSER FACP
12.8 esserbus
®
The IQ8FCT LP can be used as FCT (fire control transponder) to control and monitor external fire protection
devices like fire dampers or as a technical alarm module (TAL) to monitor an external contact *.
The transponder is a loop device and therefore has an integrated loop isolator, a contact input and a potential-
free relay output, which can be used to directly switch 230 V AC / 16 A. The transponder is powered by the field
bus and does not require external voltage supply.
To monitor the contact, the alarm and monitoring module (Part No. 804870) or an external resistance
combination can be used. The max. loop length to the contact is 500 m. The IQ8FCT LP is delivered in a robust
IP 65 protected surface mount housing.
* Zur Ansteuerung von Brandschutzeinrichtungen die lokalen und regionalen Anforderungen / Vorschriften beachten.
Fig. 54: esserbus
®
transponder IQ8FCT LP, 230 V AC
In order to control the fire protection equipment in compliance with the relevant standards, the IQ8FCT
should be installed right next to or inside the control device.
Specifications
Loop
- Nominal voltage
- Quiescent current
- Alarm current
- Number
Alarm display
Operating display
Relay contact rating
Terminals
- Contact input / loop
- Relay contact / power supply
Ambient temperature
Storage temperature
Humidity
Protection rating
Housing
Colour
Weight
Dimensions (w x h x d)
Specification
VdS approval
Declaration of Performance
For further information and accessories refer to product catalogue and documentation of the devices.
86
transponder IQ8FCT LP, 230 V AC (Part No. 808621)
:
14 V DC ... 42 V DC
:
approx. 45 µA @ 19 V DC
:
approx. 9 mA @ 19 V DC, pulsed
:
max. 127 piece per loop
:
red LED
:
green LED
:
230 V AC / 30 V DC, 16 A resistive, 8 A induct load
:
max. 2,5 mm² (AWG 26-14)
:
max. 6 mm² (AWG 30-10)
:
-20 °C ... +70 °C
:
-30 °C ... +75 °C
:
≤ 95 % (without condensing)
:
IP 65
:
PP plastic
:
grey (similar to RAL 7035)
:
approx. 250 g
:
150 x 116 x 67 (mm)
:
EN 54-17 : 2005 / -18 : 2005
:
G 209138
:
DoP-20792130701
Features
Intelligent fire control systems via programmable logics of
the inputs and outputs of the FCT
Programmable runtime monitoring for activation of fire
dampers
Optional impulse activations of the relay can be
programmed with selectable impulse lengths
Programmable fail-safe settings of the relay for protection
against failure and disruption to the fire alarm system
Feedback contact for monitoring the error-free function of
the fire control system
Switching capacity up to 230 V AC/16 A
Max. 127 transponders per loop
Power supply via fieldbus
Integrated loop isolator
Robust IP 65-protected surface-mount housing
TI 798960.GB0 / 04.20