SERIES 3000 MKIII TECHNICAL MANUAL

8.1 Default configuration

Series 3000 MkIII detectors are supplied with a default configuration as shown below. The settings for
full scale range, calibration gas level, calibration interval, inhibit current & timeout and access password
can be changed to suit individual applications.
Detector 4-20mA output signal
Fault / Under-range
Inhibit
Zero signal
Full scale
Overrange
Other settings
Inhibit time out
Calibration Interval & Display / Output. Cal Interval 180 days (selectable 30-360). Three options for overdue
Password
Gas
Oxygen
Hydrogen Sulfide
Hydrogen Sulfide
Carbon Monoxide
Sulfur Dioxide
Ammonia
Ammonia
Chlorine
Chlorine Dioxide
Nitric Oxide
Nitrogen Dioxide
Hydrogen
Hydrogen
Hydrogen Chloride 10.0 to 20.0ppm
Hydrogen Cyanide
Hydrogen Fluoride
Ozone
Phosphine
Fluorine
Ethylene Oxide
Notes:
1. Default ranges have been selected based upon recommended exposure limits set around the world.
2. Where ranges significantly above the recommended defaults are needed select a gas cal point
near to the required alarm point or between 30 and 70% of full scale. Consideration must be given
to providing adequate ventilation of the calibration gas and ensure there is no exposure of the user
to toxic levels of gas.
For details of how to change the configuration for full scale range, calibration gas level, calibration
interval, inhibit current & timeout and access password refer to section 12.
3mA
3mA (default). Selectable 4mA (toxic), 17.4mA (oxygen)
4mA
20mA
22mA
0 (no time out). Selectable 0 to 240 minutes (5 min steps). If 0 is
selected, output current is permanently inhibited.
warning indication (selectable off, via display only or via display and
3mA output).
000 (password disabled). If changed then password is activated.
Change back to 000 to de-activate.
Selectable Full
Default Range
Scale Range
25.0%/Vol only
25.0%VOL
10.0 to 50.0ppm
15.0ppm
50 to 500ppm
100ppm
100 to 500ppm
300ppm
5.0 to 20.0ppm
15.0ppm
50 to 200ppm
200ppm
200 to 1,000ppm 1,000ppm
5.0 to 20.0ppm
5.0ppm
1.00ppm only
1.00ppm
100ppm only
100ppm
5.0 to 50.0ppm
10ppm
1,000ppm only
1,000ppm
9,999ppm only
9,999ppm
10ppm
30.0ppm only
30.0ppm
12.0ppm only
12.0ppm
0.4ppm only
0.4ppm
1.2ppm only
1.2ppm
4.00ppm only
4.00ppm
20.0 to 50.0ppm
25.0ppm
Steps
Selectable Cal
Gas Range
n/a
20.9%/Vol (Fixed) 20.9%/Vol
0.1ppm
10ppm
100ppm
5.0ppm
50ppm
50ppm
5.0ppm
n/a
n/a
5.0ppm
n/a
n/a
1.0ppm
n/a
n/a
n/a
n/a
n/a
5.0ppm
18
MAN0917_Issue 6_08/2015
Default Cal
Point
10ppm
50ppm
100ppm
5.0ppm
100ppm
300ppm
2.0ppm
0.5ppm
50
30 to 70% of
selected full
5ppm
scale range
500ppm
5000ppm
5.0ppm
10.0ppm
5.0ppm
0.2ppm
0.5ppm
2.00ppm
10.0ppm