How To Replace The Battery Pack - Honeywell Touchpoint Plus Wireless User Manual

Hide thumbs Also See for Touchpoint Plus Wireless:
Table of Contents

Advertisement

Issue 1 04/19
3020M5044_1

7.1.2 How to Replace the Battery Pack

Touchpoint Plus Wireless shall not be operated with the access door unsecured when in Normal mode.
Failing to secure it properly will risk fire or explosion and will invalidate Regulatory Approval.
The battery pack has circuitry that puts it into sleep mode to save power when it is not connected and running.
Connecting it to a powered-up Touchpoint Plus Wireless causes the battery to change to active mode and it
will function normally after a short booster charge.
To replace the battery pack:
1) Ensure that the atmosphere is below flammable levels.
2) Leave the Touchpoint Plus Wireless Controller powered on.
3) Unscrew the two locking handle security screws and open the enclosure.
4) Switch the backup battery On/Off switch to Off (Fig. 31) to isolate the battery.
5) Replace the battery pack with Honeywell Analytics part no. TPPLOIBB (order number: TPPLSIBB)
6) Switch the backup battery On/Off switch back to On.
7) Close the enclosure door and secure the handle with the two security screws.
8) Switch power on and restore TPPL to normal operation.
9) Touch the power icon to check battery power levels.
Note: Ensure that the battery On/Off switch is in the On position before closing the access door or the backup
battery will not work when it is most required.