- The IP protocol reserves certain IP address ranges for special purposes (such as
multicasting). Do not assign IP addresses in the range from 127.0.0.0 –
127.255.255.255 or 224.0.0.0 – 255.255.255.255.
- This device is intended for use in applications as described in the operating in-
structions only. Using this device in non-approved applications will lead immedi-
ately to the expiration of all guarantee and warranty claims on the part of the op-
erator against the manufacturer.
.

4. Mounting the device

Caution
- This device is designed only for a operating voltage range from +7 to 36 VDC. Do
not use a higher voltage; this could destroy the Router and other devices.
- Connecting plugs should never be connected or disconnected from electrical de-
vices if they are carrying a live load. Be sure to first disconnect all poles of the plug.
Remember to disconnect all plugs from the Router before it is installed or removed.
- Electrical devices should not be installed or removed during operations. Never
install or remove the Router while it is running.
Caution
- It is important to provide sufficient clearance between devices which cause strong
electromagnetic interference (such as frequency converters, transformers or motor
regulators). The clearance gap between such devices and the Router should be as
wide as possible. The Router can be further shielded by using a mu-metal partition.
- The Router is designed to be mounted on a top-hat rail that is compliant with the
EN 50022 standard. This Router will not have a secure mount if any other type of
rail is used. Use a top-hat rail that complies with the EN 50022 standard. Be sure to
observe the mounting information provided by the manufacturer.
Note
- A minimum of 2 inch (5 cm) gap should be kept between the Router and
neighbouring devices from the top and bottom. This will ensure that the Router is
sufficiently ventilated and prevent induction from developing.
- The top-hat rail should be located in a horizontal position along the vertical rear
wall of the electrical cabinet. This ensures that the Router can be adequately venti-
lated from below to above.